Step2 Ground Connection
Remove the front cover(s) and the control terminal cover. Then follow the instructions
below to install the ground connection for the inverter.
1
Locate the ground terminal and connect an appropriately rated ground cable to
the terminals. Refer to
cable specification for your installation.
2
Connect the other ends of the ground cables to the supply earth (ground) terminal.
Note
•
200 V products require Class 3 grounding
. Resistance to ground must be < 100Ω.
•
400 V products require Special Class 3 grounding. Resistance to ground must be less
than
< 10 Ω.
Make sure to install ground connection between the equipment and the motor for safe
use. Otherwise it may cause an electrical shock and result in personal injury or even
death.
Содержание G100
Страница 14: ......
Страница 16: ...5 5 7 5 kW 3 Phase ...
Страница 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Страница 48: ......
Страница 68: ......
Страница 81: ......
Страница 100: ......
Страница 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Страница 118: ......
Страница 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Страница 140: ... PID control block diagram ...
Страница 165: ...Code and Features Description Code Description continuous rating ...
Страница 170: ......
Страница 186: ... Displayed as on the Keypad ...
Страница 200: ...provided signal output at 150 36 sec ...
Страница 216: ...Code and Features Description delay time delay time ...
Страница 219: ......
Страница 237: ......
Страница 253: ......
Страница 295: ......
Страница 314: ......
Страница 330: ...11 10 Remote Keypad Option It is comprised of a remote keypad and cables 1 m 2 m 3 m and 5 m Units mm ...
Страница 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...