UNITOUR Power System 

 

User Manual 

 

Page 33 

 

3.11

 

Advanced, Main Menu 

From the “Home Menu” tap 

LOG IN

 then touch 

ADVANCED

. T

he “Main Menu” screen opens.  

 

 

Main Menu 

Note: In all of the following menus, the SAVE button only appears if you have altered a setting. 
The altered setting is only applied when you tap SAVE. To discard the changes and retain the 
original setting tap EXIT

3.12

 

Auto Power Timing 

AutoPower is a feature that sequentially switches ON all channels set to Auto Power mode. 
This  helps  to  prevent  nuisance  tripping  of  circuit  breakers  due  to  high  in-rush  currents  on 
power-up. See section 3.6.2. 
 
The start of the switch-on sequence (also known as a staggered start) can be either manually 
triggered  from  the  touch  screen  by  selecting  the 

CONTROL 

button  (see  section  3.10)  or 

automatically triggered whenever the channels selected control signal is present. 
 
The stagger time is the time interval between each channel being switched on. The default 
stagger time is 0.5 seconds but you can set the time any time from 0.1 to 2.5 seconds. The 
“AutoPower Timing” menu (below) sets this stagger time. 
 
AutoPower channels are switched off either manually from the touch screen by tapping the 

CONTROL 

button then 

SHUT DOWN 

or automatically if they have a control source and their 

control signal is no longer present. 

A “Hold Time” can be set for the automatic shut down to  

prevent  fixtures  being  turned  off  if  there  is  a  short  interruption  to  their  control  signal.  The 
“AutoPower Timing” menu (below) sets this hold time duration. 
 
To set the AutoPower time, from the “Home Menu” tap

 LOG IN

ADVANCED

,

 AUTOPOWER 

TIMING

.  

 

Содержание UNITOUR

Страница 1: ...24 Channels 48 Channels UNITOUR with Optional Dimming User Manual LSC Control Systems 61 3 9702 8000 info lsccontrol com au www lsccontrol com au Version 2 0 December 2021...

Страница 2: ...duct is recommended to be carried out by LSC Control Systems Pty Ltd or its authorised service agents No liability will be accepted whatsoever for any loss or damage caused by service maintenance or r...

Страница 3: ...7 3 3 Phase Power Input 48 Channel Model 14 1 7 4 Power Status Indicators 15 1 7 5 Controlled Power Output Connectors 15 1 7 6 Auxiliary Power Output Connectors 15 2 Home Menu 16 2 1 Alarms and Warnin...

Страница 4: ...evel 35 3 13 4 Curves 36 3 14 View Channels 37 3 15 View Sources 38 3 16 View Logs 38 3 17 Configure Art Net 39 3 18 Configure sACN 40 3 19 Set Power Limits 40 3 20 Load Save 41 3 21 System Setting 42...

Страница 5: ...UNITOUR Power System User Manual Page 5 8 Specifications 51 9 Compliance Statements 54...

Страница 6: ...perators The dimmers have the ability to control any load including LEDs incandescent neon and fluorescent fixtures Output channels can be operated in any of the following modes AUTO POWER mode These...

Страница 7: ...e passes through the zero point of the sine wave The UNITOUR s clever software provides real time voltage and current monitoring per phase as well as load current RMS and Peak and earth leakage curren...

Страница 8: ...the UNITOUR rack Delux Model DMX512 A Outputs All DMX512 A RDM outputs are galvanically isolated to 1500 volts and short circuit protected 1 3 2 Options The UNITOUR can be supplied with the following...

Страница 9: ...oice of output connectors Socapex 19 pin Wieland 16 pole Wieland 10 pole Optional top mounted patch bay providing 2 1 parallel patching of every output plus two connectors and ammeter for load lamp te...

Страница 10: ...uto switch or a programmable MCCB 400A auto switch plus programmable RCD Two 3 phase circuit breakers 24 channel model or four 3 phase circuit breakers 48 channel models that feed the output modules T...

Страница 11: ...m See section 2 1 Solid Red UHM alarm Yellow Acknowledged alarm RESET The recessed RESET button resets the operation of the UHM All settings and configurations are retained USB connector Used for the...

Страница 12: ...onfigured in the factory or warehouse without the need for 3 phase power It only requires a PoE Ethernet switch to connect to the UHM control module which will power the UHM allowing the UNITOUR to be...

Страница 13: ...he dimmer circuitry also employs high quality and virtually silent chokes with a Rise Time of 220 S measured between 10 and 90 at 50 output level into maximum rated load In switching mode the module u...

Страница 14: ...hannel model uses 400A PowerLock In and Thru connectors PowerLock Input Connectors Earth Bonding Stud Deluxe model DMX outputs Work Light 1 Phase Auxiliary Outputs 3 Phase Auxiliary Output 3 Phase Pow...

Страница 15: ...ovided that it has both a Neutral and an Earth connection A duplicate set of Power Status indicators are located on the front panel adjacent to the master switch 1 7 4 Controlled Power Output Connecto...

Страница 16: ...ges and Currents The central section of the screen shows a real time display of the RMS voltage and currents across all 3 input phases and the neutral Voltages that are outside of the set limits are s...

Страница 17: ...that are in use are shown above the menu buttons Green Signal good Red Signal error Yellow Signal missing Grey Signal selected for use but has never been seen Menu Buttons The menu buttons at the bot...

Страница 18: ...Normal operation Yellow Error Status LED Green Normal operation Flash Red Input power fault See section 2 1 4 Yellow Over temperature warning Flashing Yellow Software update in progress Comms LED wil...

Страница 19: ...An alarm is activated if a warning level is reached Currents above the warning levels are shown in yellow See section 3 19 Hint You can also set load and leakage current warning alarms for each output...

Страница 20: ...here are 3 Levels of access to UNITOUR Each level can be PIN protected to restrict un authorised access See section 3 22 1 USER This level consists of the 6 menu buttons at the bottom of the Home Menu...

Страница 21: ...back to the factory default settings This will set all channels to Auto Power mode and LOCAL control If you tap NO and do not do a reset the output channels will remain in their last used configurati...

Страница 22: ...X control Tap DMX then NEXT Enter the DMX slot number for the first channel in the rack then tap SAVE Each subsequent channel will be patched to the next sequential DMX slot Art Net control Tap Art Ne...

Страница 23: ...s setting to isolate the power AUTO POWER These channels will act as power switches and they will be sequentially switched on to minimise in rush currents either automatically by the presence of their...

Страница 24: ...be changed by using the menu buttons at the bottom of the home screen as described below 3 4 Home Screen Menu Buttons The buttons at the bottom of the home menu provide instant access to the following...

Страница 25: ...RIGGERS ACTIVE then EXIT without saving 3 6 CHANNEL MODES From the Home Menu tap CHANNEL MODES The screen shows the current mode of each channel To change the Mode of a channel tap the channel to sele...

Страница 26: ...TROL button 3 6 3 ALWAYS ON The channel cannot be turned off except by turning off its channel circuit breaker When power is applied they will be sequentially switched on in the same manner channels s...

Страница 27: ...touch screen lights magenta and the LED above the CHANNEL SELECT button on the output module lights magenta When the required channels are selected tap a Control Source button at the bottom of the scr...

Страница 28: ...annels can be selected To select a range of channels press and HOLD the first button in the range then press the last button in the range When a channel has been selected the channel on the touch scre...

Страница 29: ...an alarm is activated See Configure Currents below If a channel breaker trips the display for that channel shows turns red and shows the load and leakage currents that were present when the breaker tr...

Страница 30: ...ed above each channel s circuit breaker Multiple channels can be selected To select a range of channels press and HOLD the first button in the range then press the last button in the range When a chan...

Страница 31: ...RCD will trip when the leakage reaches 100 This allows you to accurately see how close each channel is to its limit and to set an appropriate alarm to warn you when the limit is approaching 3 9 View L...

Страница 32: ...Channels pane allows you manually control channels that are set to Auto Power mode To start the sequential switch on sequence also known as a staggered start tap START UP To switch off all Auto Power...

Страница 33: ...gered from the touch screen by selecting the CONTROL button see section 3 10 or automatically triggered whenever the channels selected control signal is present The stagger time is the time interval b...

Страница 34: ...hold time count down can also be manually started from the CONTROL button 3 13 Dimmer Setup The DIMMER SETUP menu allows you to set the minimum level maximum level and curve for the dimmer channel s...

Страница 35: ...s below this level the dimmer will be off To set a minimum level for a channel s from the DIMMER SETUP Menu tap MIN LEVEL The previously selected channel s are still valid If you want to change your s...

Страница 36: ...nal and channel output level It defines how the dimmers output voltage responds to the control signal input UNITOUR provides several different curves and each has a different response You can try each...

Страница 37: ...ing different Curves 3 14 View Channels The View Channels menu can be used to view all of the settings for the channel that you select From the Home Menu tap LOG IN ADVANCED VIEW CHANNELS then select...

Страница 38: ...es at the input of each channel This can help you identify issues when the channel is incorrectly patched or it is set to ALWAYS OFF or ALWAYS ON Channels with no control source are shown in black CHA...

Страница 39: ...he Net Subnet and Universe values then tap SAVE Note If you are using Art Net I or Art Net II leave the Net setting at 0 zero and only use the Subnet and Universe settings Any Art Net universes curren...

Страница 40: ...ystem The priority level is set by the sACN transmitting device If UNITOUR receives more than one sACN signal on the selected universe it will only respond to the signal with the highest priority sett...

Страница 41: ...they can be exported or imported from a USB memory stick The file is known as a show and each show can be individually named using the pop up on screen keyboard To load or save a show from the home sc...

Страница 42: ...enu is used to select the IP address that is used for this UNITOUR rack The network address can be set manually known as a Static IP or it can be automatically assigned by your network using a DHCP se...

Страница 43: ...utilizes multicasting and as such the actual IP address in use is generally irrelevant 3 21 2 Configure Alarms The Configure Alarms menu lists all of the conditions that UNITOUR continuously monitors...

Страница 44: ...ange message to LSC s HOUSTON X monitoring software via the ethernet connection See section 5 Tap SAVE to keep the changes and exit To discard the changes and retain the original setting tap EXIT 3 21...

Страница 45: ...iscard the changes and retain the original setting tap EXIT 3 21 4 Set Rack Name Every UNITOUR rack can be given a name Names might indicate the physical location of the channels for example one rack...

Страница 46: ...the bottom of the Home menu see section 3 4 ADVANCED see section 3 11 SERVICE This level is always locked and requires a PIN Contact LSC for access HOUSTON This allows remote configuration and monito...

Страница 47: ...GS UPDATE FIRMWARE You are asked Are you sure you want to proceed Tap YES The screen shows the progress of the upgrade to the various modules of UNITY When the update is finished tap REBOOT to complet...

Страница 48: ...protection systems of the UNITOUR are disabled in this mode The following action will turn the channel on even if the system has shut down the output due to a dropped neutral or over voltage input To...

Страница 49: ...d Alarms can be marked as acknowledged whilst the problem is being resolved changing the indicator to yellow Any new alarms will change the indicator to flashing red again Once all alarms are cleared...

Страница 50: ...ex 19 pin multipin sockets 6 1 Dual parallel wired Wieland 16 pole Multipin Sockets Do not include pin outs due to various standards Output Circuit Numbers 1 6 1 6 7 12 7 12 13 18 13 18 19 24 19 24 25...

Страница 51: ...ion Dual Ethercon connectors with internal Ethernet switch to allow daisy chaining of multiple racks for TCP IP UDP sACN Art Net and other network protocols Single front panel mounted DMX in and thru...

Страница 52: ...00A circuit breaker controlled from UHM control module PowerLock 400A 5 wire TN S 230 415V supply in and thru CEE 32A 3 phase auxiliary power output socket Australian models fitted with 32A 3 phase ou...

Страница 53: ...of complex loads including neons motors and low wattage practicals without the need for a dummy load Current Control Technology CCT circuitry to prevent nuisance tripping of breakers due to high inru...

Страница 54: ...9 Compliance Statements The UNITOUR from LSC Control Systems Pty Ltd meets all required CE European and RCM Australian standards European Committee for Electrotechnical Standardization CENELEC Austra...