
Gen VI Dimmer
User Manual
Page 38
Either reduce the load or increase the cooling to reduce the temperature. If the fan has been set
to a constant slow speed, either increase the speed or set
it to “Automatic”. See section 5.12.3.
Also check that the fan is operating and that the sides of the dimmer are not blocked.
When the temperature drops below 86 degrees the outputs are automatically switched back on.
Touching
shows the legend for the display……
Touch anywhere within the legend window to close.
6.3
Trouble Shooting
If a channel is not working check the Circuit Breaker for that channel.
If the Circuit Breaker has tripped (OFF), firstly try to determine the cause of the breaker tripping.
It could be a blown lamp, a circuit overload or and earth leakage fault. Rectify the problem (replace
the lamp or reduce the load) then restore the Circuit Breaker. If the Circuit Breaker continues to
trip, refer the problem to a suitably qualified person.
If a channel will not turn on check the following,
•
The fade curve is not set to “Tru Power”
•
The Maximum level is not set too low
•
Ensure that the load is plugged in
•
If a custom dim curve is selected change to a S or L curve. If the channel now comes on,
check the custom curve
If a channel will not turn off check the following,
•
The Minimum level is set at 0%
•
Riggers control is set to 0%
•
Channel is not set
to “Auto Power”
6.3.1
Rigger Test
You can test the operation of a dimmer channel from the “Riggers Control” on the LCD touch
screen. See section 5.5
6.3.2
DMX Control
If the dimmer is working from the Riggers Control but not via DMX, check that the dimmer is
patched to the correct DMX slot and correctly configured for DMX control.
You can check the DMX input signal from the touch screen. See section 5.8.6