
38
Function list
5 Function list
5.1 Drive Group
LED
display
Address
for
communi-
cation
Parameter
name
Min/
Max
range
Description
Factory
defaults
Adj.
during
run
Page
0.00
A100
[Frequency
command]
0 -
400
[Hz]
This parameter sets the frequency
that the inverter is commanded to
output.
During Stop: Frequency Command
During Run: Output Frequency
During Multi-step operation:
Multi-step frequency 0.
It cannot be set greater than F21-
[Max frequency].
0.00
O
ACC
A101
[Accel time]
0 -
6000
[Sec]
During Multi-Accel/Decel operation,
this parameter serves as Accel/Decel
time 0.
10.0
O
dEC
A102
[Decel time]
10.0
O
drv
A103
[Drive mode] 0 - 3
0
Run/Stop via Run/Stop key on the
keypad
1
X
1
Terminal
operation
FX: Motor forward run
RX: Motor reverse run
2
FX: Run/Stop enable
RX: Reverse rotation
select
3 RS485 communication
Frq
A104
[Frequency
setting
method]
0 - 8
0
Digital
Keypad setting 1
0
X
1
Keypad setting 2
2
Analog
V1 1: -10 - +10 [V]
3
V1 2: 0 - +10 [V]
4
Terminal I: 0 - 20 [mA]
5
Terminal V1 setting 1 +
Terminal I
6
Terminal V1 setting 2+
Terminal I
7 RS485 communication
8 Digital Volume
St1
A105
[Multi-Step
frequency 1]
0 -
400
[Hz]
Sets Multi-Step frequency 1 during
Multi-step operation.
10.00
O
St2
A106
[Multi-Step
frequency 2]
Sets Multi-Step frequency 2 during
Multi-step operation.
20.00
O
St3
A107
[Multi-Step
frequency 3]
Sets Multi-Step frequency 3 during
Multi-step operation.
30.00
O
CUr
A108
[Output
current]
Displays the output current to the
motor.
-
-
Содержание SV-iG5H Series
Страница 1: ...Thank you for purchasing LS Variable Frequency Drives ...
Страница 14: ......
Страница 20: ...6 Installation Wiring 2 2 Dimensions SV004iG5H 2 SV008iG5H 2 SV004iG5H 4 SV008iG5H 4 SV015iG5H 2 SV015iG5H 4 ...
Страница 23: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O ...
Страница 24: ...10 Installation Wiring ...
Страница 51: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern ...
Страница 140: ...Advanced functions 126 The following pattern is shown when the H26 Number of auto restart try is set to 2 ...
Страница 174: ...Protective functions 160 ...
Страница 220: ...206 DECLARATION OF CONFIRMITY ...
Страница 224: ...210 ...
Страница 226: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 ...