Human Machine Interface Installation Guide
eXP20-TTA/DC, eXP30-TTA/DC
eXP30-TTE/DC, eXP40-TTA/DC
eXP40-TTE/DC, eXP40-TTB/DC
eXP60-TTA/DC, eXP60-TTB/DC
This installation guide provides simple function information of HMI control. Please read
carefully this data sheet and manuals before using products. Especially read safety
precautions and handle the products properly.
ȿ
Meaning of warning and caution inscription
WARNING
WARNING indicates a potentially hazardous situation which,
if not avoided, could result in death or serious injury
CAUTION
CAUTION indicates a potentially hazardous situation which,
if not avoided, may result in minor or moderate injury.
It may also be used to alert against unsafe practices
WARNING
£
Do not contact the terminals while the power is applied.
¤
Protect the product from being gone into by foreign metallic matter.
¥
Do not manipulate the battery.(Charge, disassemble, hitting, short, soldering)
CAUTION
£
Be sure to check the rated voltage and terminal arrangement before wiring.
¤
When wiring, tighten the screw of terminal block with the specified torque rage.
¥
Do not install the flammable things on surroundings.
¦
Do not use the HMI in the environment of direct vibration.
§
Except expert A/S staff, do not disassemble or fix or modify the product.
¨
Use the HMI in an environment that meets the general specifications contained
in this datasheet.
©
Be sure that external load does not exceed the rating of output module.
ª
When disposing of HMI and battery, treat it as industrial waste.
2
Use of Environment
ȿ
To install, observe the below conditions.
No
Item
Specification
Standard
1
Ambient temp.
0
50
-
2
Storage temp
-20
60
-
3
Ambient humidity
10
85%RH, non-condensing
-
4
Storage humidity
10
85%RH, non-condensing
-
5
Vibration
Resistance
Occasional vibration
-
-
Frequency
Acceleration
Amplitude
Count
IEC 61131-2
5
f<9
ภ
-
3.5mm
10 times
in each
direction
for
X, Y, Z
9
f
150
ภ
9.8
ุ
(1g)
-
Continuous vibration
Frequency
Acceleration
Amplitude
5
f<9
ภ
-
1.75mm
9
f
150
ภ
4.9
ุ
(0.5g)
-
3
Applicable Version
ȿ
For system configuration, the following version is necessary.
Windows CE
: V1.00 above
XP-Runtime/ XP-Builder
: V2.03/V2.03(B) above
ȿ
Check the battery attached in the XGT Panel.
Use
: Operating RTC when power Off
Standard
: CR2032
ȿ
Check the mounting Brackets in the box
Bracket Quantity
: 1 set(four for eXP20/30/40, Six for eXP60)
ȿ
This is appearance of the eXP. Refer to each name when driving the system. For more
information, refer to user manual.
ȿ
Dimension
>8QLWPP@
+VGO
eXP20 eXP30 eXP40 eXP60
A
102.0
132.5
154.0
218.0
B
128.0
165.0
208.0
276.2
C
92.5
123.0
137.5
201.5
D
118.5
155.5
191.5
259.5
E
5.5
5.5
7.4
F
32.0
36.1
44.4
6
Installation
ȿ
When you install the XGT Panel, a panel, designed to mount the XGT Panel inside should
be specified and allowed for.
1) Panel Cut Dimensions (Unit: mm)
+VGO
&KOGPUKQP
6QNGTCPEG
:
;
H;3
H;3
H;3
H;3
2) Mounting XGT Panel
£
Ensure that there is 100mm clearance around all sides of the panel to be affected
at a minimum by the electromagnetic wave or heat.
¤
The panel thickness (Z) should be 1.6 ~ 9.5mm.
ྛ
Insert the mounting brackets into the eXP insertion slots. Tightening the screws with
too much force can damage the product. (The recommend torque is 0.66N
ื
m)
¦
Use screwdriver to tighten brackets screw as illustration shown.
7
Wiring
ȿ
Power wiring
In case that the power is out of rated voltage, connect constant voltage transformer.
Connect the power having the small noise between cables or between earths.
In case of having lots of noise, connect the insulation transformer or noise filter.
Separate the XGT Panel power supply cable from the main circuit cable.
(high voltage and current) and input/output cable. Maintain a minimum.
separation of 100mm between cables.
8
Warranty
ȿ
Warranty period
LSIS provides an 18-month-warranty from the date of the production.
ȿ
Scope of Warranty
The troubles caused by improper condition, environment or treatment except the
instructions of LSIS.
The troubles caused by external devices.
The troubles caused by remodeling or repairing based on the user’s own discretion.
The troubles caused by improper usage of the product.
The troubles caused by the reason which exceeded the expectation from science
and technology level when LSIS manufactured the product.
The troubles caused by natural disaster.
LS ELECTRIC Co., Ltd.
www.lselectric.co.kr
10310001448 V1.4 (2020.4)
x
E-mail:
x
Headquarter/Seoul Office
Tel: 82-2-2034-4033,4888,4703
x
LS ELECTRIC Shanghai Office (China)
Tel: 86-21-5237-9977
x
LS ELECTRIC (Wuxi) Co., Ltd. (Wuxi, China)
Tel: 86-510-6851-6666
x
LS-ELECTRIC Vietnam Co., Ltd. (Hanoi, Vietnam)
Tel: 84-93-631-4099
x
LS ELECTRIC Middle East FZE (Dubai, U.A.E.)
Tel: 971-4-886-5360
x
LS ELECTRIC Europe B.V. (Hoofddorf, Netherlands)
Tel: 31-20-654-1424
x
LS ELECTRIC Japan Co., Ltd. (Tokyo, Japan)
Tel: 81-3-6268-8241
x
LS ELECTRIC America Inc. (Chicago, USA)
Tel: 1-800-891-2941
x
Factory: 56, Samseong 4-gil, Mokcheon-eup, Dongnam-gu, Cheonan-si, Chungcheongnam-
do, 31226, Korea
1
Safety Precautions
4
Accessory
5
Parts name and Dimension
ɂ
E
A
Front Part
A
ɂ
E
A
Status LED
A
ɂ
E
A
USB Device(eXP30/40/60)
A
ɂ
E
A
Insertion Slots
A
ɂ
E
A
USB Host
A
ɂ
E
A
Battery Cover
A
ɂ
E
A
Power Terminal
A
ɂ
E
A
Ethernet Terminal
A
ɂ
E
A
COM3 Connector
A
ɂ
E
A
COM1,COM2 Connector
A
ɂ
E
A
Dip Switch Settings
A
ɂ
E
A
&20&20&RQQHFWRU
,WHP
H;3
H;3
H;3
H;3
5DWHGYROWDJH
'&9
er man
er man
er man
er man
e
£
ual
nu
n l
nn l
nnual.
u
nn
ȿ
ȿ
¦
¦
¦
¦ §
ȿ
;*7 33DQHO
¨ © ª «
¦
¦
¦
¦
¦
¦
¦ §
§
§
§
¦
¦
¦
¦ §
§
§
§
&GHCWNV5GVVKPIU
7UGT5GVVKPIU
ȉ
0Q$CVVGT[QPQHH
¬
G:2
G:2
:2
G:2
G:2
©
¨
G:2
G:2
%0
Panel
HMI
Driver
Bracket Screw
B
k t S
B
k t S
Bracket Body
HMI Case
HOLE