5. Handling and Operation
5-16
5.2.13
Manual Speed Command Offset Correction
[Cn-12]
This calibrates the offset value of analog speed commands manually. Example: -10
The range of adjustable speed command analog voltage is from +1 V to -1 V. If offset voltage
exceeds this range, [oVrnG] Over Range is displayed and there is no compensation.
You can check the corrected offset value in the analog speed offset [P2-18].
[Example of handling manual speed command offset correction]
Order
Loader Displays
Keys to Use
What to Do
1
Press [MODE] to display [Cn-00].
2
Press [UP] or [DOWN] to move to
[Cn-12].
3
Press [SET] to enter offset correction.
4
Press [SET] to enter offset correction
setting.
The current offset value displayed.
5
Press [UP] or [DOWN] to adjust the
value.
6
or
Press [SET] to save the adjusted
offset value.
[Done] is displayed.
If you press [MODE] and it will not be
saved.
7
Press [MODE] for a second to return
to [Cn-12].
※
“ ” indicates flickering.