Connecting the Cables
58
4.4
Ground Connection
Install ground connections for the inverter and the motor by following the correct specifications to
ensure safe and accurate operation. Using the inverter and the motor without the specified
grounding connections may result in electric shock.
•
Do not use the ground terminal as the signal (control) ground.
•
Do not share the ground connection with other machines that consume a large amount of
power, such as a welding machine.
•
Connect the ground cable to the nearest earth contact and keep the cable length as short as
possible.
Because the inverter is a high-frequency switching device, leakage current may occur during
operation. To avoid the danger of electrocution due to current leakage, the inverter must be
properly grounded. Ground connection must be made to the specified ground terminal on the
inverter. Do not connect ground cables to chassis screws.
Note
•
200 V products require Class 3 grounding. Resistance to ground must be ≤ 100 Ω.
•
400 V products require Specia
l Class 3 grounding. Resistance to ground must be ≤ 10 Ω.
The following table lists the minimum ground cable specifications that must be met to properly
ground the inverters.
Inverter Capacity
Grounding wire size ( mm²)
200 V class
400 V class
0.75
–
3.7kW
4
2.5
5.5
–
7.5 kW
6
4
11
–
15 kW
16
10
18.5
–
22 kW
25
16
30
–
45 kW
25
16
55
–
75 kW
35
35
90
–
110 kW
-
60
132
–
220 kW
-
100
280
–
315 kW
-
185
375 kW
-
240
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...