Communication Function
354
11.4
Basic Settings
Before proceeding with setting communication configurations, make sure that the
communication lines are connected properly. Turn on the inverter and set the communication
parameters.
Group
Code
LCD Display
Parameter Setting
Setting Range
Unit
COM
01
Int485 St ID
-
1
1
–
250
-
02
Int485 Proto
0
ModBus RTU
0
–
3
-
03
Int485 BaudR
3
9600
0
–
5
bps
04
Int485 Mode
0
D8 / PN / S1
0
–
3
-
05
Resp Delay
-
5
0
–
1000
ms
Communication Parameters Setting Details
Code
Description
COM-01 Int485
St ID
Sets the inverter station ID between 1 and 250.
COM-02 Int485
Proto
Select one of the two built-in protocols: Modbus-RTU and LS INV 485
Setting
Function
0
Modbus-RTU
Modbus-RTU compatible protocol
1
Reserved
Not used
2
LS INV 485
Dedicated protocol for the LS inverter
COM-03 Int485
BaudR
Sets a communication setting speed of up to 38,400 bps.
COM-04 Int485
Mode
Set a communication configuration. Set the data length, parity check method,
and the number of stop bits.
Setting
Function
0
D8/PN/S1
8-bit data / no parity check / 1 stop bit
1
D8/PN/S2
8-bit data / no parity check / 2 stop bits
2
D8/PE/S1
8-bit data / even parity / 1 stop bit
3
D8/PO/S1
8-bit data / odd parity / 1 stop bit
COM-05 Resp
Delay
The built-in 485 communication (Modbus-RTU or LS INV 485) device performs
as a slave. The slave iS7 responds to the master after the period of time set in
this function code.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...