Communication Function
352
11.2
Specifications
Category
Specifications
Communication method RS-485
Transfer form
Bus type, Multi-drop link system
Inverter type name
SV-iS7 series
Converter
Embedded with RS-232
Number of connected
inverters
Maximum of 16
Transfer distance
Maximum 1,200 m (recommended distance: within 700 m)
Recommended cable
size
0.75 mm2 , (18AWG), Shielded twisted-pair (STP) wire
Installation type
Dedicated terminals (S+/S-/SG) on the control terminal block
Communication Power
Supplied by the inverter -
insulated power source from the inverter’s
internal circuit communication power (supplied from the inverter)
Communication Speed
1,200/2,400/9,600/19,200/38,400 bps
Control procedure
Asynchronous communications system
Communication system Half duplex system
Letter system
Modbus-RTU: BINARY/LS Bus: ASCII
Stop bit length
1-bit/2-bit
Sum check
2 byte
Parity check
None/Even/Odd