Using Protection Features
336
Group
Code
LCD Display
Parameter Setting
Unit
OUT
31
–
33
Relay 1,2, Q1
6
IOL
-
Note
A warning signal output can be provided in advance by the multi-function output terminal before
the inverter overload protection function (IOLT) operates. When the overcurrent time reaches 60%
of the allowed overcurrent (150%, 1 min), a warning signal output is provided (signal output at 150%
for 36 sec).
10.2.4
Keypad Command Loss
When setting operation speed using the keypad, speed command loss setting can be used to
select the inverter operation for situations when the speed command from the keypad is lost
due to the disconnection of signal cable.
Group
Code
LCD Display
Parameter Setting
Unit
PRT
11
Lost KPD Mode
2
Free-Run
-
OUT
31
–
33
Relay1,2, Q1
30
Lost Keypad
-
DRV
06
Cmd Source
0
Keypad
-
CNF
22
Multi Key Sel
0
JOG Key
-
Speed Command Loss Setting Details
Code
Description
PRT-11 Lost KPD
Mode
Set the DRV-06 (command source)
to “
0 (keypad)
”
, and s
elect the inverter’s
operation for when there is a keypad connection problem.
Setting
Function
0 None
The speed command immediately becomes the
operation frequency without any protection function.
1 Warning
Set one of the output terminals to
“2
9 (Lost keypad)
”
to
output a relevant warning signal when abnormal
operating conditions arise.
2 Free-Run
The inverter blocks output when the keypad connection
is lost. The motor performs in free-run condition.
3 Dec
The motor decelerates and then stops at the time set at
PRT-07 (Trip Dec Time) when the keypad connection is
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...