Using Monitor Functions
Code
Description
output is as shown in the graph below.
Group Code LCD Display
Parameter
setting
Unit
OUT
58
FDT Band (Hz) - 10.00
Hz
2
FDT-2
Outputs a signal when the set frequency and detected
frequency (FDT frequency) are equal, and fulfills the FDT-1
condition at the same time:
[
Absolute value
(set frequency
–
detected frequency) <
detected frequency width /2 ] & [ FDT-1 ] condition is
met
The detected frequency width is 10 Hz. When the detected
frequency is set to 30 Hz, the FDT-2 output is as shown in
the graph below.
Group Code LCD Display
Parameter
setting
Unit
OUT
57
FDT
Frequency
-
30.00
Hz
58
FDT Band (Hz) -
10.00
Hz
3
FDT-3
Outputs a signal when the operating frequency meets the
following condition:
Absolute value
(detected frequency
–
output frequency)
< detected frequency width /2
Содержание SV-iS7 Series