![LS ELECTRIC SV-iS7 Series Скачать руководство пользователя страница 329](http://html1.mh-extra.com/html/ls-electric/sv-is7-series/sv-is7-series_user-manual_1943801329.webp)
Using Monitor Functions
312
9.3.3
Voltage Output (-10
–
+10V) Using an I/O Expansion Module
If the optional I/O expansion module is installed, the operating status can be monitored using
the bipolar voltage output of the I/O expansion module.
Group
Code
LCD Display
Parameter Setting
Unit
OUT
14
AO3 Mode
0
Frequency
-
15
AO3 Gain
-
100.0
%
16
AO3 Bias
-
0.0
%
17
AO3 Filter
-
5
Msec
18
AO3 Const %
-
0.0
%
19
AO3 Monitor
-
0.0
%
Voltage Output (-10
–
+10 V) Details
Code
Description
OUT-14 AO3
Mode
The output mode can be set identically to when the AO1 voltage output is used.
However, because bipolar voltage output is possible for AO3, unipolar (0
–
+10V) or
bipolar (-10
–
+10V) voltage can be produced according to the type of the output
variable.
Examples of bipolar output voltages are as follows.
Output Direction
Related Functions
F)
/Reverse(-)
0: Frequency
9: Ramp Freq
10: Speed Fdb
12: PID Ref Value
13: PID Fdb Value
14: PID Output
Reverse(-)
/Regenerative(-)
4: Torque
7: Iqss
-
OUT-15 AO3
Gain, OUT-
16 AO3 Bias
The graph below illustrates how the analog voltage output (AO3) changes
depending on the OUT-15 (AO3 Gain) and OUT-16 (AO3 Bias) values.
The Y-axis is analog output voltage (-10
–
+10V), and the X-axis is a percentage of the
output. For example, if the maximum frequency set at DRV-20 (Max Freq) is 60 Hz
and the present output frequency is 30 Hz, then the x-axis value on the next graph is
50%.
OUT-08 AO3 Gain
OUT-16
100.0% (Factory Default)
80.0%
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...