voltage is 20 V lower than the operating voltage set at ADV-79.
If the set value for ADV-79 is lower than the DC link voltage when the inverter is in normal
operation, the DB resistor may overheat due to continuous DB resistor operation.
Conversely, if the set value at ADV-79 is much higher than the DC link voltage range, an overvoltage
trip may occur because the DB resistor does not operate when it is needed.
Example) If the input voltage is 440 V and the value at ADV-79 is set to 600 V, the DB resistor
operates when the inverter is on because the DC link voltage is 622 V. Since the voltage level that
stops the DB resistor is 590 V, the DB resistor may overheat due to continuous DB resistor
operation.
8.44
kW/HP Unit Selection
Select the units between kW and HP for the capacity of the inverter and motor.
Group Code Name
LCD Display
Parameter Setting
Setting Range
Unit
DRV
30
kW/HP unit
selection
KW/HP Select
0 kW
0-1
-
1 HP
8.45
Output Voltage Drop Prevention
This function is used to prevent voltage drop in the inverter output by decreasing the
current output, thereby taking advantage of the expanded command zone of the
output voltage, if the input voltage drops or overload conditions arise.
Group Code Name
LCD Display
Parameter Setting
Setting Range
Initi
al
ADV
87
OVM Mode
OVM Mode Sel
0 No
0-1
0:No
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...