3-Wire Operation
The 3-wire operation latches the signal input (the signal stays on after the button is released),
and is used when operating the inverter with a push button.
Group Code
Name
LCD Display
Parameter Setting Setting Range Unit
DRV
06
Command source Cmd Source
1 Fx/Rx - 1
0
–
5
-
IN
65
–
75
Px terminal
configuration
Px Define(Px:
P1
–
P8 [optional:
P9
–
P11])
14 3-Wire
0
–
51
-
To enable the 3-wire operation, the following circuit sequence is necessary. The minimum input
time (t) for 3-wire operation is 1 ms, and the operation stops when both the forward and
reverse operation commands are entered at the same time.
[Terminal connections for 3-wire operation]
[3-wire operation]