![LS ELECTRIC SV-iS7 Series Скачать руководство пользователя страница 183](http://html1.mh-extra.com/html/ls-electric/sv-is7-series/sv-is7-series_user-manual_1943801183.webp)
Basic Functions
166
Group Code Name
LCD Display
Parameter Setting
Setting Range
Unit
frequency
BAS
08
Acc/Dec
reference
Ramp T Mode 0 Max Freq
Max Freq/Delta
Freq
-
09
Time scale
Time scale
1 0.1
0
–
2 (0.01/0.1/1)
sec
Acc/Dec Time Based on Maximum Frequency
–
Setting Details
Code
Description
BAS-08 Ramp T
Mode
Set BAS-08
to “0
(Max Freq)” to setup
acc/dec time based on maximum
frequency.
Configuration
Description
0
Max Freq
Set the acc/dec time based on the maximum frequency.
1
Delta Freq Set the acc/dec time based on the operating frequency.
If, for example, the maximum frequency is 60.00 Hz, the acc/dec times are set
to 5 seconds, and the frequency reference for operation is set at 30 Hz (half of
60 Hz). Therefore, the time required to reach 30 Hz is 2.5 seconds (half of 5
seconds).
BAS-09 Time scale
Use the time scale for all time-related values. It is particularly useful when
more accurate acc/dec times are required, due to load characteristics, or
when the maximum time range needs to be extended.
Configuration
Description
0
0.01 sec
Sets 0.01 second as the minimum unit.
1
0.1 sec
Sets 0.1 second as the minimum unit.
2
1 sec
Sets 1 second as the minimum unit.
Note that the range of maximum time values may change automatically when the units are
changed. If for example, the acceleration time is set to 6000 seconds, a time scale change from 1
second to 0.01 second will result in a modified acceleration time of 60.00 seconds.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...