![LS ELECTRIC SV-iS7 Series Скачать руководство пользователя страница 175](http://html1.mh-extra.com/html/ls-electric/sv-is7-series/sv-is7-series_user-manual_1943801175.webp)
Basic Functions
158
7.5.2
The Terminal Block as a Command Input Device (Fwd/Rev run
commands)
Multi-function terminals can be selected as a command input device. This is configured by
setting DRV-
06 (command source) to “1 (Fx/Rx
-1
)”. Select two terminals for the forward and
reverse operations, and then set the relevant codes (2 of the 11 multi-function terminal codes,
IN-65
–
75 for P1
–
P8 [optional: P9
–
P11]
) to “1 (Fx)” and “2 (Rx)” respectively. This application
enables both terminals to be turned on or off at the same time, constituting a stop command
that will cause the inverter to stop operating.
Group Code
Name
LCD Display
Parameter Setting Setting Range Unit
DRV
06
Command source
Cmd Source
1
Fx/Rx-1
0
–
5
-
IN
65
–
75
Px terminal
configuration
Px Define(Px:
P1
–
P8 [optional:
P9
–
P11])
1
Fx
0
–
51
-
2
Rx
88
Delay time setting
Run On Delay
-
1.00
0.00
–
100.00
Sec
Fwd/Rev Command by Multi-function Terminal
–
Setting Details
Code
Description
DRV-06 Cmd Source
Set to “1 (Fx/Rx
-
1)”.
IN-65
–
75 Px Define
Assign a terminal for forward (Fx) operation.
Assign a terminal for reverse (Rx) operation.
IN-88 Run On Delay
Set the delay time if the inverter operation needs to be synchronized with
other sequences. When the run command input (Fx/Rx) is given, the
operation begins after the set time has elapsed.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...