Technical specifications
374
Use Class H or RK5 UL listed input fuses and UL listed circuit breakers only.
See the table above for the voltage and current ratings for the fuses and
breakers.
10.6 Terminal screw specifications
Input/output terminal screw specifications
Product (kW)
Terminal screw size
Torque (Kgf
c m/Nm)
3-Phase
400 V
5.5
M4
7.1–12.2/0.7–1.2
7.5
11
M5
30.6–38.2/3–3.8
15
18.5
M6
61.2–91.8/6–9
22
Control circuit terminal screw specifications
Terminal
Terminal screw size
Torque(Kgf
cm/Nm)
FX/RX/BX/RST/P1–P7/CM
M2.6
4.0/0.4
V1, I1/AO1/AO2/CM/
A1/A2/A3/A4/C1/C2/C3/C4/GND
M2
2.2–2.5/0.22–0.25