Detailed operation by function groups
226
6.5.7.4 Emergency stop deceleration time (FUN_51) and
emergency stop terminal input low pass filter (FUN_52)
If any emergency arises during operation, you can use the BX (emergency stop)
signal input at the terminal block to stop the motor operation immediately. Once
the BX input is provided, the motor decelerates based on the “Emergency stop
deceleration gradient” set at FUN_51, and then it stops. If the motor cannot
complete a full-stop within the set time, it continues to perform a free-run stop. If
you need to allow to motor to free run as soon as the BX signal input is provided,
set FUN_51 to “0”.
Also, set the time constant for the low pass filter at FUN_52 (BX Termi LPF) to
avoid noise interference if the noise level is high at the installation site.
Code
Keypad display
Name
Range
Unit
Default setting
FUN_51 BX Time
Emergency stop
deceleration time
0.0–6000.0
sec
0.0
FUN_52 BX Termi LPF
Emergency stop terminal
input low pass filter
0–2000
ms
0
<BX time (FUN_51) set to “0”>