Detailed operation by function groups
172
6.3.2 Multifunction digital input terminal
6.3.2.1 Defining the multifunction digital input terminal P1–P7
(DIO_01–DIO_07)
Codes DIO_01 to DIO_07 are used to define the multifunction digital input
terminals P1to P7. The following table lists the functions available for these
multifunction digital input terminals.
Only one function may be assigned to one terminal at a time, and the setting
cannot be changed during operation. If you try to assign a function to more than
one terminal, the setting will not be saved on the second terminal, and its original
function will be retained.
Multifunction terminal settings may not be changed during an operation, and
their utilization may be restricted depending on the control mode set at PAR_07
No
Fault trips
Keypad display
PAR_07 Control Mode
Speed(IM)
V/F
Slip Comp Speed (PM)
1
Speed-L
Multistep speed-L
O
O
O
O
2
Speed-M
Multistep speed-M
O
O
O
O
3
Speed-H
Multistep speed-H
O
O
O
O
10
Xcel-L
Multistep acc/dec-L
O
O
O
O
11
Xcel-H
Multistep acc/dec-H
O
O
O
O
13
Ext Trip-B
External trip B terminal
O
O
O
O
17
Timer Input Timer input
O
O
O
O
19
ASR Gain
Sel
ASR gain switching
O
X
X
O
22
PreExcite
Pre-excitation
O
X
X
X
25
Use Trq
Bias
Use torque bias
O
X
X
O
26
A3 Safety
Use auxiliary reference
O
O
O
O
Содержание LSLV-L100 Series
Страница 16: ...3 Preparing the Installation Preparation ...
Страница 36: ...Installing the Inverter 23 Installation Power terminal and control terminal wiring diagram ...
Страница 240: ...Detailed operation by function groups 227 Operation Details BX time FUN_51 set to a value other than 0 ...
Страница 252: ...Detailed operation by function groups 239 Operation Details stops When forward operation has a lighter load ...
Страница 339: ...326 Communication features CAN message frame versions CAN 2 0A CAN 2 0B ...
Страница 395: ...382 ...