![LS ELECTRIC LSLV-H100 Series Скачать руководство пользователя страница 200](http://html1.mh-extra.com/html/ls-electric/lslv-h100-series/lslv-h100-series_user-manual_1943798200.webp)
187
Learning Advanced Features
5.10 Damper Operation
A damper is a device that controls the flow in a ventilation system. If a fan and a damper are
used together in a system, the inverter may be configured to operate according to the
damper’s operation status. During a damper operation, one of the relay outputs
OUT-31
–35
(Relay 1
–5) may be set to ‘33 (Damper Control)’ to output a signal based on the damper’s
operation status. O
ne of the multi-function terminal inputs (IN-65
–71) may also be set to ‘45
(Damper Open)’ to receive the damper status input. The inverter starts operating when both
the run command and the damper open signal are turned on (relay output setting at
OUT-
31
–35 is not necessary)
.
When the time difference between the inverter run command and the damper open signal
exceeds the delay time set at AP2-45 (Damper DT), damper error (Damper Err) occurs. If
the damper open relay output and damper control input are set at the same time, and if the
damper open signal is not received until the time set at AP2-45 (Damper DT) is elapsed
(when the inverter is not operating), damper error (Damper Err) occurs.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range Unit
AP2
45
Damper check
time
Damper DT
-
0.1
–600.0
sec
IN
65-71
P1
–7 Px
terminal
configuration
P1
–P7
Define
45
(Damper open)
-
-
OUT
31-35
Multi-function
relay 1
–5
Relay 1
–5
33
(Damper Control)
-
-
Damper Operation Setting Details
Code
Description
AP2-45 Damper DT
Sets the damper open delay time.
Detects the inverter run command or the damper open signal
(whichever is received first) and outputs a damper error (Damper Err) if
the other signal is not received until the time set at AP2-45 elapses.
IN-65
–71 P1–7
define
Sets one of the multi-
functional terminals to ’45 (Damper Open)’ to
enable damper operation.
OUT-31
–35 Relay
1
–5
Sets one of the relay outputs to ’33 (Damper Control)’ to provide a
relay output when the inverter run command is turned on.
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...