5.8.2 Soft Fill Operation
A soft fill operation is used to prevent excessive pressure from building in the pipe system at
the initial stage of a pump operation. When the operation command is given, a general
acceleration (without PID control) begins and continues until the output reaches the
frequency set at AP1-21, for the time set at AP1-22. Then, the soft fill PID operation is
performed unless the feedback value has reached the value set at AP1-23 (Soft Fill Set
value). The soft fill PID operation continues until the feedback or the soft fill PID reference
value reaches the value set at AP1-23 (Soft Fill Set value). When the soft fill operation ends,
a normal PID operation starts.
Group Code
Name
LCD Display
Parameter
Setting
Setting Range Unit
AP1
20
Soft Fill options
Soft Fill Sel
0
No
0
–1
-
21
Pr- PID operation
frequency
Pre-PID Freq 30.00
Low Freq
–
High Freq
Hz
22
Pre-PID duration
Pre-PID
Delay
60.0
600.0
sec
23
Soft fill escape
value
Soft Fill Set
20.00
Unit Min
–Unit
Max
%
24
Soft fill reference
increment
Fill Step Set
2.00
0
–Unit Band %
25
Soft fill reference
increment cycle
Fill Step
Time
20
0
–9999
sec
26
Soft fill feedback
difference
Fill Fdb Diff
0.00
0
–Unit Band %
Soft Fill Operation Setting Details
Code
Description
AP1-20
Soft Fill Sel
Enables or disables the soft fill PID.
AP1-21
Pre-PID Freq
Sets the frequency range for a general acceleration without PID control. If
AP1-21 (Pre-PID Freq) is set to 30 Hz, general operation is performed until
the PID feedback reaches the value set at AP1-23 (Soft Fill Set). However,
if the PID reference or feedback exceeds the value set at AP1-23 during
the pre-PID operation, a normal PID operation starts immediately.
AP1-22 Pre-PID
Delay
In general, a PID operation starts when the feedback volume (controlled
variables) of PID controller exceeds the value set at AP1-23. However, if
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...