![LS ELECTRIC LSLV-H100 Series Скачать руководство пользователя страница 143](http://html1.mh-extra.com/html/ls-electric/lslv-h100-series/lslv-h100-series_user-manual_1943798143.webp)
130
Learning Basic Features
4.17.2 Stop After DC Braking
When the operation frequency reaches the set value during deceleration (DC braking
frequency) the inverter stops the motor by supplying DC power to the motor. With a stop
command input, the inverter begins decelerating the motor. When the frequency reaches
the DC braking frequency set at ADV-17, the inverter supplies DC voltage to the motor and
stops it.
Group Code
Name
LCD Display Parameter Setting
Setting Range Unit
ADV
08
Stop mode
Stop Mode
1
DC Brake
0
–4
-
14
Output block time
before braking
DC-Block
Time
0.00 0.75~90kW
0.00
–60.00
sec
2.00 110~500kW
15
DC braking time
DC-Brake
Time
1.00
0
–60
sec
16
DC braking
amount
DC-Brake
Level
50
0
–200
%
17
DC braking
frequency
DC-Brake
Freq
5.00
0.00
–60.00
Hz
DC Braking After Stop Setting Details
Code
Description
ADV-14 DC-
Block Time
Set the time to block the inverter output before DC braking. If the inertia of
the load is great, or if DC braking frequency (ADV-17) is set too high, a fault
trip may occur due to overcurrent conditions when the inverter supplies DC
voltage to the motor. Prevent overcurrent fault trips by adjusting the output
block time before DC braking.
ADV-15 DC-
Brake Time
Set the time duration for the DC voltage supply to the motor.
ADV-16 DC-
Brake Level
Set the amount of DC braking to apply. The parameter setting is based on
the rated current of the motor.
ADV-17 DC-
Brake Freq
Set the frequency to start DC braking. When the frequency is reached, the
inverter starts deceleration. If the dwell frequency is set lower than the DC
braking frequency, dwell operation will not work and DC braking will start
instead.
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...