110
Learning Basic Features
4.9 Reset and Restart
Reset and restart operations can be setup for inverter operation following a fault trip, based
on the terminal block operation command (if it is configured). When a fault trip occurs, the
inverter cuts off the output and the motor will free-run. Another fault trip may be triggered if
the inverter begins its operation while motor load is in a free-run state. In PRT-08, bit 1 sets
the option for all the fault trips, other than low voltage trips, and bit 2 sets the option for low
voltage trips. PRT-10 sets the delay time for restart (the time for the inverter to wait before it
restarts).
The number of auto-restarts (PRT-09) refers to the number of times the inverter will try
restarting its operation. If fault trips occur again after restart, the retry number counts down
each time the inverter restarts until the number becomes ‘0.’ Once the inverter restarts
successfully after the initial fault trip, the inverter does not restart until the next fault trip
occurs. The number of auto-restarts set at PRT-09 that decreased after a restart reverts to
the original setting value if successful operation continues for certain period of time.
Group Code Name
LCD
Display
Parameter Setting
Setting
Range
Unit
DRV 06
Command source
Cmd
Source
1 Fx/Rx-1
0
–5
-
PRT
08
Reset restart setup
RST
Restart
00
00
–11
Bit
09
No. of auto restart
Retry
Number
6
0
–10
-
10
Auto restart delay
time
Retry
Delay
5.0
0.1
–600.0
sec
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...