Protect Switch 400V motors
Version:
3.0 | 14.02.2021
instruction manual | 1162723-00000
page
16
from
29
5.1.3
Motor protection ELR (-Q1)
5.1.3.1
Overview of component with description of the individual lamps and switches
5.1.3.2
Setting current limitation (parametrization
– rated current setting)
Press the reset button (11) for longer than 6 s to enter the "Parameterization" operating mode. The
green PWR LED (7) flashes once.
To differentiate from other operating states, the LEDs are switched off for 0.3 s at intervals of 2 s in
parameter assignment mode.
Adjust the rated voltage of the drive using the 240°potentiometer (6).
The rated current is specified in 16 stages. The four LEDs display the set rated voltage.
Store the value by pressing the Reset button (11) again (non-volatile area of the data memory).
If you press the reset button for longer than 2 s (and less than 6 s), the set current is displayed for 3 s.
This function is only possible if the component is not triggered and there is no error on the component.
6
Potentiometer for rated current
parametrization
7
LED PWR: Control supply voltage
8
LED ERR: Message/fault
9
LED L: Anti-clockwise
10
LED R: Clockwise
11
Reset-button