The 

LPS     PP - 2/110 Series

 are Surge Protective Device (SPD) for 

maximum 5 amps DC Power Supply. The Standard Clamping Voltage 

is:

LPS     PP - 2 / 110 SERIES
INSTALLATION INSTRUCTIONS

                    TECHNICAL SUPPORT

  T: +603-7980 5911   E: [email protected]

       

150V for PP - 2/110 

PP - 2/110

Product Series

Number of 

Protected Wires

Maximum Operating 

Signal Voltage

Safety Precautions & Installation Procedures

1. Do not install during thunderstorm.

2. Turn Off power supply to all equipment to be protected.

3. Verify that the equipment chassis is earthed.

4. Add a 2.5mm    green ground wire to G of 

equipment terminal

 of 

    SPD and connect the other end (with cable lug) to the metal 

    chassis equipment by;
     i. Removing a screw on the metal chassis that is within reach of the

        ground wire.     

     ii. Removing any paint around the screw hole.

     iii. Tightening screw with ground wire cable lug under it.

     iv. If equipment has no metal chassis, connect the ground wire to

          the nearest power socket earth / earthed metal equipment rack / 

          earthed metal bracket which support the equipment.