The
LPS POE-8 Series
are Surge Protective Device (SPD) for Power
over Ethernet. The Standard Clamping voltage is 9.5V (Line - Line) &
33V (Line - Earth) for data while power is:
LPS POE-8 SERIES
INSTALLATION INSTRUCTIONS
TECHNICAL SUPPORT
T: +603-7980 5911 E: [email protected]
22V for POE-8/12 39V for POE-8/24 82V for POE-8/48
Safety Precautions & Installation Procedures
1. Do not install during thunderstorm.
2. Turn Off power supply to all equipment to be protected.
3. Verify that the equipment chassis is earthed.
4. Add a 2.5mm green ground wire to G of
equipment terminal
of
SPD and connect the other end (with cable lug) to the metal
chassis equipment by;
i. Removing a screw on the metal chassis that is within reach of the
ground wire.
ii. Removing any paint around the screw hole.
iii. Tightening screw with ground wire cable lug under it.
iv. If equipment has no metal chassis, connect the ground wire to
the nearest power socket earth / earthed metal equipment rack /
earthed metal bracket which support the equipment.
5. Cut and ensure that the incoming data line and DC power cable is
less than 1 meter away from the equipment.
6. Strip about 50mm of cable jacket to expose wires.
7. Strip about 6mm of wire insulator to expose conductor.
2
Содержание POE-8 Series
Страница 4: ......