L-IP User Manual
126
LOYTEC
Version 6.1
LOYTEC electronics GmbH
Max Send Time
This parameter influences the heart beat functionality in the twin router object of the
diagnostic node. If set to 0 the heart beat functionality is disabled, any other value will
enable heart beat functionality and
nvoTwinStatus
will be sent out with the interval defined
by this value.
Figure 125: The Parameters View.
Min Redundant Send Time
This value defines the twin router monitoring interval. It must be identical on both twin
routers.
Max Retries
This value defines the number of retries used by the twin router monitoring algorithm if the
twin router does not respond. Thus, the maximum time it takes until a twin router failure
will be detected calculates to:
)
1
Re
(
Re
tries
Max
dTime
dundantSen
Min
ectionTime
FailureDet
TwinRouter
History Size
This value defines the number of monitoring intervals used to compare the number of
packets forwarded by both twin routers. It must be identical on both twin routers.
Warning Limit
This value defines the limit for issuing the “Forwarding Warnings” (see
nvoTwinStatus
,
Section 9.7.4 or alarm log, Section 9.6.3): If the number of packets forwarded by the local