L-INX User Manual
285
LOYTEC
Version 4.0
LOYTEC electronics GmbH
Table 15: Properties of the Device Object.
1
Only available if the device is a BACnet/IP-BACnet MS/TP router.
13.3.1.1
Device Name and ID
The following properties of the Device object, which are part of every BACnet object,
identify the device uniquely.
Object_Identifier (Read-Only).
This property, of type
BACnetObjectIdentifier
, is a
numeric code that is used to identify the object. For the Device object, the object identifier
must be unique internetwork-wide.
The
Object_Type
part of the
Object_Identifier
of the Device object is 8 (= DEVICE). The
instance part of the
Object_Identifier
of the Device object is configurable via the
configuration UI (see Section 4.2.11). The default value is 17800.
Object_Name (Read-Only).
The name of the object. The value of
Object_Name
of the
Device object is configurable via the configuration UI (see Section 4.2.11). For the Device
object, this name shall be unique within the BACnet internetwork.
Object_Type (Read-Only).
The object‘s type. For the Device object, the value of this
property is 8 (= DEVICE).
13.3.1.2
Device Information
A whole set of properties provides general purpose information about the device.
Vendor_Name (Read-Only).
The value of this property is ―LOYTEC electronics GmbH‖.
Vendor_Identifier (Read-Only).
A numerical value identifying the BACnet vendor. The
value of this property is 178.
Model_Name (Read-Only).
The value of this property is equal to the product code of the
device. Examples are ―LINX-200‖ or ―LINX-221‖.
Firmware_Revision (Read-Only).
The value of this property gives the current firmware
version of the device.
Application_Software_Version (Read-Only).
The value of this property gives the build
date and the version of the current firmware.
Location (Read-Writable).
A string intended to be used to describe the physical location
of the device, e.g., ―1st floor‖. This property can be set via the configuration UI (see
Section 4.2.11). The default value is ―unknown‖.
Description (Read-Only).
A string intended to be used to describe the device‘s purpose.
This property can be changed via the configuration UI (see Section and 4.2.11).
Protocol_Version (Read-Only).
The BACnet protocol version supported by the device.
The value of this property is 1.
Protocol_Revision (Read-Only).
The BACnet protocol revision of the BACnet version
supported by the device. The value of this property is 5.
Protocol_Services_Supported (Read-Only).
A string of bits marking which BACnet
services can be executed by the device. For a detailed list of the BACnet services supported,
please refer to the product‘s PICS document.
Protocol_Object_Types_Supported (Read-Only).
A string of bits identifying which
BACnet object types are supported by the device. For a detailed list of supported object
types, please refer to the product‘s PICS document.