background image

I331 

GB 

08 

18

                                               31100158

GB

Insulation 

Rated insulation voltage Ui                                 250V

Rated impulse withstand voltage Uimp               6kV

Power frequency withstand voltage                    4kV

Connections

Type of terminals                                                Screw (fixed)

Number of terminals                                           3 for Aux supply / measure

Conductor cross section (min… max)                2.5 - 16 mm

2

(see below for AWG)

Tightening torque                                                2 - 2.2 Nm (26.5lbin)

Pulse output connections

Type of terminals                                                Screw (fixed)

Number of terminals                                           2

Conductor cross section (min… max)                0.5 - 4 mm

2

(20-10 AWG)

Tightening torque                                                1.3 Nm (12.1lbin)

Housing

Version                                                                2 modules (DIN 43880)

Mounting                                                             35mm DIN rail (IEC/EN 60715)

                                                                           or by screw using extractible clips

Material                                                               Polyamide RAL 7035

Degree of protection                                           IP40 on front 

‚

                                                                           IP20 terminals

Weight                                                                 148 g

Certifications and compliance

Certifications                                                       cULus, EAC, RCM

UL marking 

Supply/measure connections    AWG Range: (14 - 6 AWG - stranded) 

   (14 - 10 AWG - solid)
   Field wiring terminals tightening torque: (26.5lb.in)

Pulse output connections    AWG range:   (20 - 10AWG)  

   Field wiring terminals tightening torque: (12.1lb.in)

Comply with standards                                       IEC/EN 61010-1, IEC/EN 61010-2-030, EN 50470-1, 

                                                                           UL 61010-1, CSA C22.2 n° 61010-1

‚

To comply with the protection requirements the meter must be mounted in a class IP51 enclosure or better. 
(IEC/EN 60529).

TECHNICAL CHARACTERISTICS

Standard version

Rated voltage Us                                                 220 - 240V

Operating voltage range                                      187 - 264V

Rated frequency                                                  50 - 60Hz

Operating frequency range                                  45 - 66Hz

Power consumption/dissipation                          7VA  /  0.45W

A120 version

Rated voltage Us                                                 110 - 120V

Operating voltage range                                      93 - 132V

Rated frequency                                                  60Hz

Operating frequency range                                  54 - 66Hz

Power consumption/dissipation                          7VA /  0.45W

Current

Minimum current (Imin)                                     0.5A

Transition current (Itr)                                        1A

Reference current (Iref - Ib)                                10A

Max current (Imax)                                             63A

Start current (Ist)                                                40 mA

Accuracy

Active energy (IEC/EN 62053-21)                       Class 1

LED pulse

Integration constant                                            1000 pulses / kWh  

Pulse length                                                        30ms

Static output

Number of pulses                                               Programmable 1-10-100-1000 pulses / kWh  

Pulse length                                                        100ms

External voltage                                                   10 - 30VDC

Max current                                                         50mA

Ambient conditions

Mounting                                                             Indoor use only

Operating temperature                                        -25...+55°C

Storage temperature                                           -25...+70°C

Relative humidity                                                <80% non-condensing (IEC/EN 60068-2-78)

Maximum pollution degree                                 2 

Overvoltage category                                          III

Altitude                                                                

2000m

Climatic sequence                                               Z/ABDM (IEC/EN 60068-2-61)

Shock resistance                                                 10g (IEC/EN 60068-2-27)

Vibration resistance                                            0.7g (IEC/EN 60068-2-6)

Mechanical environment                                     Class M1

Electromagnetic environment                             Class E1

6

Содержание DME D120 T1

Страница 1: ... consumption active power Programmable static output for pulse or alarm threshold ATTENZIONE Leggere attentamente il manuale prima dell utilizzo e l installazione Questi apparecchi devono essere installati da personale qualificato nel rispetto delle vigenti normative impiantistiche allo scopo di evitare danni a persone o cose Prima di qualsiasi intervento sull apparecchio rimuovere eventuali tensi...

Страница 2: ... della accuratezza dell energy meter INDICAZIONE FLUSSO DI ENERGIA Quando lo strumento sta rilevando un flusso di energia verso il carico il display visualizza nell angolo in alto a destra una icona rotante Quando il carico non richiede energia attiva oppure quando la corrente assorbita è inferiore alla corrente di avviamento l icona rotante scompare USCITA STATICA ISOLATA PROGRAMMABILE L uscita s...

Страница 3: ...k CLEAR P clearing of partial energy meters CLEAR h clearing of partial hour counter if enabled CLEAR d clearing of max demand values if enabled SETUP parameter programming setup INFO revision and checksum of internal software ESC returns to normal operation 5 To select a function press while the required function is displayed 6 If the button is never pressed for 60 consecutive seconds the display...

Страница 4: ...ined by P 03 is higher than P 04 end de activates when its value becomes less than P 06 maximum limit with hysteresis If P 04 P 06 then output activates when the measure defined by P 03 is lower than P 04 end activates when its value becomes higher than P 06 minimum limit with hysteresis P 03 Selection of measure to compare with thresholds P 04 e P 05 Threshold and delay for output activation Note...

Страница 5: ... 5 MECHANICAL DIMENSIONS mm 5 43 7 63 35 8 90 44 7 92 5 DIMENSIONI MECCANICHE mm WIRING DIAGRAMS O1 O1 Static output 30VDC 50mA max L L N O1 O1 L LOAD N L LINE N L L N O1 O1 L L O1 N O1 _ NPN out PNP out SCHEMI DI COLLEGAMENTO ...

Страница 6: ...1 To comply with the protection requirements the meter must be mounted in a class IP51 enclosure or better IEC EN 60529 TECHNICAL CHARACTERISTICS Standard version Rated voltage Us 220 240V Operating voltage range 187 264V Rated frequency 50 60Hz Operating frequency range 45 66Hz Power consumption dissipation 7VA 0 45W A120 version Rated voltage Us 110 120V Operating voltage range 93 132V Rated fre...

Страница 7: ...mento deve essere installato in contenitore con grado di protezione minimo IP51 IEC EN 60529 CARATTERISTICHE TECNICHE Versione standard Tensione nominale Us 220 240V Limiti di funzionamento 187 264V Frequenza nominale 50 60Hz Limiti di funzionamento 45 66Hz Potenza assorbita dissipata 7VA 0 45W Versioni A120 Tensione nominale Us 110 120V Limiti di funzionamento 93 132V Frequenza nominale 60Hz Limi...

Отзывы: