The window alarm works in this manner:
In the "RELAY CLOSED IN THE WINDOW" mode
- The relay is activated when the measure >= to the low threshold and <= to the high threshold.
- The relay is deactivated when the measure is < than the low threshold or > than the high threshold.
In the "RELAY CLOSED OUT OF WINDOW" mode
- The relay is deactivated when the measure >= to the low threshold and <= to the high threshold.
- The relay is activated when the measure is < than the low threshold or > than the high threshold.
2.6) Analogical output
In standard the device provides one analogical output, insulated and configurable. It can by /S2 option be equipped
with a second insulated output. The two outputs are configurable independently of each other. They can also be used as
a b/- 10V output (see "special functions" next page and
p18
for wiring).
Configurable output parameters:
- Type of output: Current output (mA) or Voltage output (V) with strap connected (see
p15
).
- Low and high output scales.
- Response time.
- Limitation.
- Monitored value: voltage, peak voltage (only for output 1 on a CPL35L), current, frequency,
plus active power, reactive power, apparent power, power factor, on a CPL35.
- Low and high input measure scales.
The
limitation
allows to bound the output signal swing to the configured output scales for all input signal values.
The
response time
allows a smoothing of the output. It is configurable from 0 to 60 s (set to 0 s at the factory).
The
hold time
is the time for the detected peak voltage measurement to be maintained on the output 1. It is configur-
able from 0,01 to 60 s (set to 1 s at the factory). This configuration rubric is only visible if the user has chosen the
PEAK VOLTAGE measure to be monitored.
2.7) Display
This rubric permits to personalize the measurements display on the front.
The display parameters are:
- Display filter.
- Decimal point display mode.
DISPLAY CONFIGURATION?
(Y-N)
Press the ‘Y’ key to access display configuration.
DISPLAY FILTER?
1 s
Enter the filter value (0 to 60 s).
Event
Alarm
Security: relay closed in alarm
Security: relay closed out of alarm
Delay before activation
Delay before deactivation
active
Relay off
Relay on
Relay on
Relay off
inactive