Hi Alarm relay action, no Hysteresis
Alarm tripped
Alarm reset
Alarm tripped
Alarm reset
Alarm = Hi
Setpoint = 69
Hysteresis = 20
20 Hyst value
Alarm = Hi
Setpoint = 69
Hysteresis = 0
Set.Pt Value
Set.Pt Value
Hi Alarm relay action with Hysteresis
The alarm relay will activate when the measured value is at or above the setpoint value.
The alarm relay will reset whe you fall below the setpoint value
The alarm relay will activate when the measured value is at or above the setpoint value.
The alarm relay will reset whe you fall below the setpoint value by the hysteresis amount
Hi
Set..p
Hyst
Mode Setpoint value Hysteresis = 0
Hi
Set.p
Hyst
Mode Setpoint value Hysteresis