LogiCO2 Power Barrier 0482 Скачать руководство пользователя страница 1

Installation Instruction

0482 Power Barrier

ENGLISH

Power Barrier for LogiCO2 Safety System.

Important!

Retain this instruction manual for future 

reference: Please read these instructions 

carefully prior to start-up and use. Failure to 

follow any of these instructions could void 

product warranties. LogiCO2 assumes no 

responsibility for claims arising out of improper 

or careless use or handling of it’s products.

Technical specifications

Power supply:

 

24V DC, from the alarm 

 system

Current consumption:

  2 x 17 mA (Supply from  

 

two  v   power supplies) 

Humidity:

 0-90% 

non-condensing

Approval:

 

CE: Emission tests according 

 

SS-EN 61000-6-3 and the 

 

immunity tests according to 

 SS-EN 

61000-6-2.

Ambient temperature:

 0 to +40°C (+32°F to +102°F)

Dimensions (LxWxD):

  90 x 161 x 38 mm / 

 

3.5” x 6.3” x 1.5”

Ingress protection:

 

IP54 according to TÜV, 

 

IP44 according to UL

Function

The LogiCO2 Power Barrier enables you to connect 

multiple power supplies (up to eight) in one system. 

Each power supply has an output of 1 A insuring that 

the power limits are not exceeded on the cables and 

connectors in each loop. The Power Barriers still 

allows each separated sensor to communicate with 

the Central Unit.
Power to the Power Barrier is supplied from the safety 

system.

Indicators

The upper green LED indicates that the left cable is 

connected to power. The lower green LED indicates 

that the right cable is connected to power. Both LEDs 

must be on for proper function.

Assembly

If the cover of the Power Barrier needs to be 

removed, please observe the following order of screw 

reassambling.

1

2

3

4

5