10
Settings
10.1
Operator interface
The operator interface is parameter driven and enables the user to change parameters and
to verify the status and history of the water heater.
When you press [MENU] once, parameters
001
to
120
can be accessed. All other
parameters can be accessed when you press [MENU] for 10 seconds.
For more information about how to use the operator interface, refer to Operator interface
(see 3.1) and Set a parameter value (see 4.1).
10.2
Parameters
Parameter Description
Unit/Value Adjustable Range
Default
001
Turn the water heater on or off.
Off
ON
Yes
Off
- water heater off
(OFF mode)
ON
- water heater on
(ON mode)
Off
002
Setpoint ON-mode
ºC
Yes
40
…max setpoint
(1)
65
003
Hysteresis
ºC
Yes
2
…
15
10
004
Turn setpoint EXT-mode (005)
on or off.
ENA
dIS
Yes
ENA
- Enable
dIS
- Disable
dIS
005
(2)
Setpoint EXT-mode 2
ºC
Yes
40
…max. setpoint
(1)
70
101
/
102
Actual water temperature
°C
No
0
…
99
-
109
Actual Ionisation signal
μA
No
0
…
15
-
112
Status EXT contact
OPE
CLo
No
OPE
- EXT contact open
CLo
- EXT contact closed
-
113
Status air proving switch
OPE
CLo
No
OPE
– air proving switch open
CLo
- air proving switch closed
-
115
Actual fan speed
x10 rpm
No
0
…
990
-
0312582_EcoSword_V4.0, 03-05-2021
57
Содержание EcoSword LGC 160-210 G P CE
Страница 11: ...User part 0312582_EcoSword_V4 0 03 05 2021 11 ...
Страница 12: ...12 ...
Страница 14: ...14 User part ...
Страница 16: ...16 User part ...
Страница 22: ...22 User part ...
Страница 25: ...Installation Maintenance and Service part 0312582_EcoSword_V4 0 03 05 2021 25 ...
Страница 26: ...26 User part ...
Страница 34: ...34 Installation Maintenance and Service part ...
Страница 56: ...56 Installation Maintenance and Service part ...
Страница 68: ...68 Installation Maintenance and Service part ...
Страница 85: ...13 4 Electrical wiring diagram 0312582_EcoSword_V4 0 03 05 2021 85 ...
Страница 90: ...90 Installation Maintenance and Service part ...
Страница 93: ......