37
10.19
C
63
CERTIFIED FLUE SYSTEMS
In general, Water heaters are certified with their own purpose supplied Concentric or Twin Pipe flue systems, C
63
certified appliances allow the
installer to use other flue systems when installing the Water heater however, they must be of a suitable minimum standard as per Table below.
CE string
flue gas
material
Eur
opean
standar
d
Temper
a-
tur
e
class
Pr
essur
e
class
R
esistance
to
condensat
e
C
or
rosion
resistance
class
Metal:
lin
er
specification
s
Soot
fir
e
resistance
class
D
istance
to
combu
stible
mater
ial
Plastics:
location
Plastics:
fir
e
behaviour
Plastics:
enclosur
e
Min required PP EN 14471
T120 P1
W
1
O
30
I of E
C/E
L
Min
required
Inox
EN 1856-1
T120 P1
W
1
L20040
O
40
C63
FLUE SYSTEM SPECIFICATION
Twin-pipe Flue Systems
Material
Water heater
d
nom
D
outside
d
inside
L
insert
PP
SHW35-SHW61
80
80 +/-0.3
81 +/-0.6
50 +20/ -2
PP
SHW86-SHW146
100
100 +/-0.3
101+/-0.6
50 +20/ -2
Concentric Flue Systems
Material
Water heater
d
nom
D
outside
d
inside
L
insert
PP
SHW35-SHW61
80/100
80 +/-0.3-124 +0.5/-1
81 +/-0.6-125.5 +1/-0.5
56 +/-3
PP
SHW86-SHW146
100/150
100 +/-0.3 - 148.5 +0.5/-1
101+/-0.5 - 150+1/-0.5
50 +20/ -2
When installing the water heater as a Type C63 appliance, it should be noted that the terminals
must not be installed on opposite sides of the building.
The maximum allowable recirculation rate is 10% under wind conditions
Aluminium flue pipe must not be used on this appliance as it may lead to premature failure of the
heat exchanger and will invalidate the warranty.
CONDENSATE
DRAIN
Condensate can flow back to the appliance, this will travel through the heat exchanger into the condensate drain via the trap.
If the flue system rises at an angle of at least 3
(50mm per metre), no additional condensate drain will be required. Failure to provide an
adequate rise in the flue system may lead to pooling of condensate which may lead to premature failure of the flue system.
Model Number
SHW35-245CE
SHW46-325CE
SHW61-325CE
SHW86-410CE
SHW116-410CE
SHW146-410CE
FLUE DATA TYPE C
63 WITH TWIN-PIPE FLUE
Minimum flue gas temp
°C
35
Average flue gas temp
°C
70
Maximum flue gas temp
°C
120
Maximum equivalent length
m
48
Model Number
SHW35-245CE
SHW46-325CE
SHW61-325CE
SHW86-410CE
SHW116-410CE
SHW146-410CE
FLUE DATA TYPE C
63 WITH CONCENTRIC FLUE
Minimum flue gas temp
°C
35
Average flue gas temp
°C
70
Maximum flue gas temp
°C
120
Maximum equivalent length
m
24
10
Содержание EcoShield SHW116-410CE
Страница 2: ...2 ...
Страница 9: ...9 EXPLODED VIEW DRAWINGS ...
Страница 27: ...27 Max distance between brackets ...
Страница 28: ...28 ...
Страница 29: ...29 ...
Страница 34: ...34 ...
Страница 47: ...47 13 9 LADDER DIAGRAM LADDER DIAGRAM ...
Страница 71: ...71 NOTES ...
Страница 72: ...72 N ...