12.13
SETTING THE MAINTENANCE SPECIFICATIONS
The following figures describe how to check and program the maintenance settings. The standard factory setting
for this function is “OFF”.
FIGURE 12.18
SETTING MAINTENANCE ALERTS
MAINTENANCE SETTINGS
The unit can be programmed in such a way that an automatic maintenance message is displayed.
There are three options that can be selected. A maintenance message appears after:
* A programmed date is reached.
* An amount of burning hours is reached.
* An amount of ignition cycles is reached.
A single option can be activated or all three options.
Operating screen:
H E A T I N G : S T A N D - B Y
> > > : 1 2 3 . 4
o
C ( 1 2 3 . 4
o
C )
Press [MENU]
Select "Maintenan" using [◄] & [►] and press [ENTER]
M a i n
M e n u
M a i n t e n a n
M a i n t e n
R e s e t
Press [▲] to reset the:
Counter for the total amount of burning hours.
Counter for the total amount of ignition cycles.
(The text will flash once briefly after resetting).
Operating screen:
M a i n t e n
M o d e
flashing second line.
Press [▲] or [▼] to change the selected
flashing option.
Screen: Selecting of all maintenance options.
M a i n t e n
M o d e
A l
l
Press [►] to set:
The option that is flashing can be changed using by [▲] & [▼]
* Date for the Maintenance message.
* Total amount of burning hours for the Maintenance message.
* Total amount of ignition cycles for the Maintenance message.
After selecting one of these values the boiler returns to the
maintenance operating screen.
Confirmation screen:
A r e
y o u
s u r e
<
C a n c e l
;
>
C o n f
i r m
Press [◄] to cancel the changes or [►] to confirm the
Press [ENTER] to confirm the changes.
changes. After the boiler returns to operating screen.
Press [ENTER]
What is flashing at the second line (before a selection is made) is the active
maintenance option.
> > > Continued on next page < < <
Содержание CP-M Series
Страница 5: ...5 2 0 PRINCIPAL PARTS FIGURE 2 1 REMOVABLE COMPONENTS CP M 60...
Страница 6: ...6 FIGURE 2 2 REMOVABLE COMPONENTS CP M 60 CONTINUED...
Страница 8: ...8 FIGURE 2 3 REMOVABLE COMPONENTS CP M 80 CP M 100...
Страница 9: ...9 FIGURE 2 4 REMOVABLE COMPONENTS CP M 80 CP M 100 CONTINUED...
Страница 11: ...11 FIGURE 2 5 REMOVABLE COMPONENTS CP M 120...
Страница 12: ...12 FIGURE 2 6 REMOVABLE COMPONENTS CP M 120 CONTINUED...
Страница 14: ...14 FIGURE 2 7 REMOVABLE COMPONENTS CP M 150 CP M 180...
Страница 15: ...15 FIGURE 2 8 REMOVABLE COMPONENTS CP M 150 CP M 180 CONTINUED...
Страница 94: ...94...