Figure 6-4 Pressure Drop vs. Flow
Table 6B Sizing Information for Temperature Rise Applications_20°F, 30°F, 40°F, 60°F and 80°F
FTX725-850
FTX400-600
0 ft
1 ft
2 ft
3 ft
4 ft
5 ft
6 ft
7 ft
8 ft
9 ft
10 ft
11 ft
12 ft
13 ft
14 ft
15 ft
0 ft
1 ft
2 ft
3 ft
4 ft
5 ft
6 ft
7 ft
8 ft
9 ft
10 ft
11 ft
12 ft
13 ft
14 ft
15 ft
Pr
essur
e Dr
op
(Feet of
Head)
Flow Rate
HEX Pressure Drop
(Full Flow Application)
FTX725-850
FTX400-600
TEMPERATURE RISE APPLICATIONS
Model
MINIMUM
PIPE
SIZE
20°F 30°F
40°F
60°F
80°F
GPM
FT/HD
GPM
FT/HD
GPM
FT/HD
GPM
FT/HD
GPM
FT/HD
400
2"
39
3.5
26
2.8
20
2.5
13
2.4
10
2.3
500
2"
49
4.8
33
3.4
24
2.9
16
2.5
12
2.4
600
2"
59
4.4
39
3.2
29
2.8
20
2.5
15
2.3
725
2 1/2"
71
4.9
47
3.5
35
3.0
24
2.7
18
2.6
850
2 1/2"
83
5.7
55
3.9
41
3.3
28
2.8
21
2.6
6
Hydronic piping
(continued)
Installation & Operation Manual
Содержание 500
Страница 55: ...55 8 Field wiring continued Figure 8 3 Low Voltage Field Wiring Connections Installation Operation Manual ...
Страница 60: ...60 Figure 10 2 Operating Instructions 10 Start up Installation Operation Manual ...
Страница 78: ...78 Figure 13 1 Wiring Diagram 13 Diagrams Installation Operation Manual ...
Страница 79: ...Figure 13 2 Ladder Diagram 13 Diagrams continued 79 Installation Operation Manual ...