4
Sidewall direct venting
(continued)
All vent pipes and air inlets must terminate
at the same height to avoid possibility of
severe personal injury, death, or substantial
property damage.
Multiple vent/air terminations
1. When terminating multiple FTXL’s terminate
each vent/air connection as described in this manual
(FIG. 4-6A).
2. Place wall penetrations to obtain minimum clearance of
12 inches (305 mm) between vent pipe and adjacent air
inlet elbow, as shown in FIG. 4-6B for U.S. installations.
For Canadian installations, provide clearances required
by CSA B149.1 Installation Code.
3. The air inlet of a FTXL is part of a direct vent connection.
It is not classifi ed as a forced air intake with regard to
spacing from adjacent boiler vents.
Figure 4-6A Multiple Vent Terminations w/
Field Supplied Fittings (must also comply with
Figure 4-1A)
WARNING
4. Mount and secure the vent plate to the wall using stainless
steel screws.
5. Seal all gaps between the pipes and wall. Seal around the
plate to the wall assuring no air gaps.
6. Assemble the vent cap to the vent plate (see FIG.’s 4-5B
and 4-5C). Insert the stainless steel screws into the vent
cap screw hole openings and securely attach the vent cap
to the vent plate.
7. Seal all wall cavities.
8. PVC/CPVC terminations are designed to accommodate any
wall thickness of standard constructions per the directions
found in this manual.
9. Stainless steel terminations are designed to penetrate walls
with a thickness up to 9.25 inches of standard construction.
Figure 4-5B PVC/CPVC Sidewall Termination Assembly
Model
Air
Vent Centerline
Width
400 - 600 4" (102 mm) 4"(102 mm)
5 5/8" (143 mm)
725 - 850 4" (102 mm) 6" (152 mm)
7 3/4" (197 mm)
Table 4B Sidewall Vent Centerline Dimensions
Figure 4-5C Polypropylene Sidewall Termination Assembly
Figure 4-6B Multiple Vent Terminations (must also
comply with Figure 4-1B)
Installation & Operation Manual
Содержание 500
Страница 55: ...55 8 Field wiring continued Figure 8 3 Low Voltage Field Wiring Connections Installation Operation Manual ...
Страница 60: ...60 Figure 10 2 Operating Instructions 10 Start up Installation Operation Manual ...
Страница 78: ...78 Figure 13 1 Wiring Diagram 13 Diagrams Installation Operation Manual ...
Страница 79: ...Figure 13 2 Ladder Diagram 13 Diagrams continued 79 Installation Operation Manual ...