Littelfuse Industrial Shock Block SB6100 Скачать руководство пользователя страница 15

 

SB6100 Industrial Shock Block

 

Page 13 

    Rev. 1-I-071520 

 

 

 

FIGURE 13.  SB6100 Temperature Derating Curve. 

 
4.  UL 943C Requirements 

  The following sections contain  excerpts  from  the  

UL 943C

(1)

 Standard for Class C and D applications.  For 

EGFPD models, only Section 4.1 applies where selectable 

trip levels  from  6  to 100 mA  are  permitted  

(20 mA is the only allowed trip level for GFCI devices in 

NEC applications). 

 

4.1  Trip Time 

  Class C and Class D GFCIs shall be capable of 

interrupting the electric circuit to the load when the fault 

current to ground (

I

) is within the range of a minimum of 

20 mA through a maximum of (110% of the rated 

voltage/500  Ω)

  A

  within the time interval (

T

) in 

accordance with the relationship: 

 

 

 

  Where: 

 

  T is expressed in seconds, and  

  I is expressed in mA 

 

  Except that T is not required to be less than 20 ms. 

 

  The tripping threshold of these GFCIs shall be in the 

range of 15 to 20 mA.  

 

  Fig. 14 shows the Class-A GFCI maximum-trip-time-

versus-current curve defined by UL 943 (with the above 

formula); UL 943 also defines a limit to the formula, with 

a minimum required trip time (or fastest trip speed) of  

20 ms, which occurs at about 300 mA of ground-fault 

current (I) per the formula.  Class C and D GFCIs must 

operate within this same curve, except that their operating 

threshold is 15 to 20 mA (non-adjustable).  See Fig. 15.  

The SB6100 EFGPDs described in this manual also 

operate within the Class-A  formula, but have a 6-  to  

100-mA threshold setting range. 

 

4.2  Grounding Circuit 

  The equipment grounding circuit of the circuit shall be 

sufficiently low impedance that, should a fault to ground 

occur, the voltage resulting across the grounding circuit 

shall not exceed 150 V.    The size of the grounding 

conductor required for a circuit shall be determined by 

calculating the resistance using the following formula and 

converting that value to a wire gauge based on the length 

of the equipment grounding conductor: 

 

  

 

  Where: 

 

 

R

G

  is  the resistance of the equipment  grounding 

conductor 

 

R

U

 is the resistance of the ungrounded conductor, and 

 

V

LG

  is the RMS value of the supply line to ground 

voltage 

 

  Refer to UL 943C Appendix A for a sample calculation 

of grounding conductor size. 

 

Содержание Industrial Shock Block SB6100

Страница 1: ...1 800 832 3873 E mail relays littelfuse com Littelfuse com SB6100 SB6100 MANUAL INDUSTRIAL SHOCK BLOCK REVISION 1 I 071520 Copyright 2020 by Littelfuse Inc All rights reserved Document Number PM 1500...

Страница 2: ...nical Specifications 19 7 1 SB6100 19 7 2 AC6000 Cart 21 7 3 AC6000 MNT 21 8 Ordering Information 21 Appendix A SB6100 Revision History 22 LIST OF FIGURES FIGURE PAGE 1 UL GFCI Classes 1 2 Three Phase...

Страница 3: ...r 1 1 1 SB6100 GFCI GFCI models are permanently connected GFCIs that meet the requirements of the UL 943 definition for Class A devices with a fixed 6 mA trip level It is available only for 208 Vac sy...

Страница 4: ...equired voltage and current ratings necessary for the application SB6100 installation should be performed by a qualified person 2 1 Mounting 2 1 1 Open Chassis Models SB6100 XX0 0 Open chassis models...

Страница 5: ...ons and can be implemented if desired for Class A GFCI or EGFPD models Use only a Littelfuse termination device as others may not meet performance requirements Each SB6100 GFCI is supplied with a 1N53...

Страница 6: ...SB6100 Industrial Shock Block Page 4 Rev 1 I 071520 FIGURE 2 Three Phase Connection Diagram GFCI Configuration Shown...

Страница 7: ...SB6100 Industrial Shock Block Page 5 Rev 1 I 071520 FIGURE 3 SB6100 311 0 Enclosed Model Lid not shown...

Страница 8: ...SB6100 Industrial Shock Block Page 6 Rev 1 I 071520 FIGURE 4 Open Chassis Model SB6100 310 0 Outline and Mounting Details...

Страница 9: ...SB6100 Industrial Shock Block Page 7 Rev 1 I 071520 FIGURE 5 Enclosed Model SB6100 311 0 Outline and Mounting Details...

Страница 10: ...SB6100 Industrial Shock Block Page 8 Rev 1 I 071520 FIGURE 6 SB6100 Operator Interface AC6000 OPI 00 Outline and Mounting Details FIGURE 7 SB6100 Operator Interface AC6000 OPI 00 Faceplate...

Страница 11: ...SB6100 Industrial Shock Block Page 9 Rev 1 I 071520 FIGURE 8 Enclosed Model SB6100 XX1 0 Bottom View Terminal Block Locations FIGURE 9 1N5339B Zener Diode and SE TA6 SM Termination Devices...

Страница 12: ...SB6100 Industrial Shock Block Page 10 Rev 1 I 071520 FIGURE 10 SE TA6 Termination Assembly FIGURE 11 SE TA6ASF WL Small Format Termination Assembly with Wire Leads...

Страница 13: ...and 100 of the trip level For an EGFPD the trip level can be selected from 6 to 100 mA For a GFCI the trip level is fixed at 6 mA Class A or 20 mA Class C and D Table 1 describes the operation of the...

Страница 14: ...When supply voltage to the SB6100 is removed the contactor will open and the green PWR and EN LEDs will turn off For a short supply outage of approximately 20 seconds the SB6100 will remain powered u...

Страница 15: ...the above formula UL 943 also defines a limit to the formula with a minimum required trip time or fastest trip speed of 20 ms which occurs at about 300 mA of ground fault current I per the formula Cla...

Страница 16: ...erruption of the circuit under both of the following conditions a An open grounding circuit and b Impedance in the grounding circuit that would allow more than a 150 volt drop in the grounding circuit...

Страница 17: ...priority over undervoltage i e if both conditions occur at the same time the INP LED will stay on indicating a miswire until the connection is fixed then it will flash if the undervoltage condition st...

Страница 18: ...SB6100 Industrial Shock Block Page 16 Rev 1 I 071520 FIGURE 16 AC6000 CART 00 Outline...

Страница 19: ...SB6100 Industrial Shock Block Page 17 Rev 1 I 071520 FIGURE 17 AC6000 MNT 00 Outline...

Страница 20: ...SB6100 Industrial Shock Block Page 18 Rev 1 I 071520 FIGURE 18 AC6000 CART with SB6100 Installed...

Страница 21: ...10 20 30 40 50 60 70 80 90 and 100 mA Trip Time Defined by or minimum 20 ms See Section 4 1 Wiring and Torque Requirements Input Terminals Conductor Size 14 to 2 0 AWG 2 08 to 67 4 mm2 Torque 14 to 2...

Страница 22: ...hipping Dimensions SB6100 XX0 0 Open Chassis Models Height 508 mm 20 0 in Width 406 mm 16 0 in Depth 203 mm 8 0 in SB6100 XX1 0 Enclosed Models Height 550 mm 21 6 in Width 490 mm 19 2 in Depth 240 mm...

Страница 23: ...and any cable and accessories 2 Includes the AC6000 MNT 00 7 3 AC6000 MNT Maximum Holding Weight 1 40 kg 90 lb Dimensions Height 705 mm 28 0 in Width 648 mm 25 5 in Depth 152 mm 6 0 in Shipping Dimens...

Страница 24: ...SECTION 7 SECTION 8 Class A GFCI models added REVISION 1 H 032618 SECTION 2 Section 2 2 1 removed Fig 3 removed all other Figures renumbered GENERAL SB6100 enclosure has been changed to grey REVISION...

Страница 25: ...ION 2 AC6000 CART 00 and AC6000 MNT 00 figures added SECTION 7 AC6000 CART 00 Section 7 2 and AC6000 MNT 00 Section 7 3 specifications added SECTION 8 AC6000 CART 00 AC6000 OPI 00 and AC6000 MNT 00 ad...

Отзывы: