PF-2123-1LDx-UG-02
Page 1 of 19
April 2017
3-Phase, Dual-Input, 12.5kW
Power Supply System
USER GUIDE
Страница 1: ...PF 2123 1LDx UG 02 Page 1 of 19 April 2017 3 Phase Dual Input 12 5kW Power Supply System USER GUIDE...
Страница 2: ...s and data are subject to change without notice Contents Introduction 3 General Safety Convention 3 Required Tools for Installation and Maintenance 3 Unpacking and Checklist 3 Equipment Inspection 4 P...
Страница 3: ...Startup Guide General Safety Convention This user guide uses the safety conventions described below Ensure that you follow the safety instructions in this guide and observe its directives to protect y...
Страница 4: ...ou have received all the items as specified by the shipping paperwork Equipment Inspection After unpacking the equipment inspect it for damage that might have resulted from shipment Check for the item...
Страница 5: ...ut with a Lite On rack adapter it can be mounted into an OCP 21 inch rack The mounting location s of the power shelf in the rack depends whether the rack is a single or dual power zone power system Th...
Страница 6: ...as shown below 3 As show below install the front bracket part number 825604 over the top of the previously installed support brackets using two 2 M5 screws for each side Note the power shelf is shown...
Страница 7: ...color WARNING Sixteen 16 M8 Linking Bus bolts are included with the Power Shelf use only these bolts to install the Linking Bus Bars The use of incorrect bolts could cause the bus bars to short out wh...
Страница 8: ...een 16 M8 Linking Bus bolts are included with the Power Shelf use only these bolts to install the Linking Bus Bars The use of incorrect bolts could cause the bus bars to short out which could result i...
Страница 9: ...re than 50 pounds Use two or more people to move the Power Shelf and to install the Power Shelf into the rack To Install the Power Shelf into the Rack Caution Two people are required to install the Po...
Страница 10: ...ng Bus bolts for each Linking Bus Bar connect each Linking Bus Bars to its corresponding bus bars in the rack Do not tighten them yet Refer to the illustration below 2 After all Linking Bus Bars have...
Страница 11: ...Dx 3 Phase 12 5kW Power System PF 2123 1LDx UG 02 Page 11 of 19 April 2017 2 Slide the Sliding Cover over the bus bars and bolts Refer to the illustration below Sliding Cover Bus Bar Cover Extended Bu...
Страница 12: ...M6 front panel mounting bolts to 8 N m 5 9 ft lbs Input Power Connections There are two input power connectors on the rear of the power shelf The input power connections for model PF 2123 1LDM EU mar...
Страница 13: ...ntains AC power for L1 L2 L3 Frame Ground and Neutral The connector is P N C532P6S by HUBBELL 3 Phase 5 Wire System Power Source Values with neutral Note The values in the tables below are from the pe...
Страница 14: ...N supports two different types of power systems 1 Delta power system or 2 Y connection 4 wire power system These systems are shown in more detail below 1 Delta power system where input voltage is 200...
Страница 15: ...s circuit breaker is off 2 Insert the two 2 input power connectors into their matching receptacles 3 For model PF 2123 1LDN twist the input power connectors in matching receptacle until they lock into...
Страница 16: ...s into place 2 Slide the remaining PSUs into the empty slots in the Power Shelf until they click into place To remove a Power Supply Unit Lift the spring latch on the front of a PSU pull the handle an...
Страница 17: ...ttery Backup System BBS is a separate shelf with multiple slots for Li ion Backup Battery Units BBUs that provides DC backup power for the Power System WARNING To prevent risk of electrical shock to p...
Страница 18: ...port to one of the communication ports on the BBS 9 Turn on power to the shelf Warranty If you experience any problems with your Lite On equipment contact Lite On Power Systems Solutions at 1 469 331...
Страница 19: ...69 331 9838 www liteon pss com email pss sales liteon com Lite On Power System Solutions No 90 Chien 1 Rd Chung Ho Dist New Taipei City 23585 Taiwan 886 2 2226181 ext 5026 www liteon pss com email pss...