background image

SCU 800 
d-LIST Control Unit 

The   sensor   control   unit   SCU   800   is   the   central 
supervisory element for the d-LIST-system. It provides 
up to two d-LIST sensor cables with power, performs 
the cyclic addressing of the connected sensors every 
10   seconds,   acquires   the   temperature   values 
measured by each sensor and evaluates the data with 
reference to various criteria.
A fire alarm is generated if either a given maximum 
threshold is exceeded, or if an increase in temperature 
takes   place   within   a   certain   time   (differential 
evaluation). The two thresholds (set-points) can be set 
individually for each of the attached sensor cables.

The measurement resolution of 0,1° gives the system a high sensitivity. The tried and tested algorithms used in 
the evaluation eliminate false alarms due to natural temperature variations.
Alarms are indicated by LEDs on the front-panel and via floating contacts to a fire terminal station (fire control  
panel), host computers or other transmission systems. Hereby, alarms generated by the two sensor cables are 
signalled individually.
Resetting takes place via an external signal from the fire terminal station or by pressing the front-panel mounted  
reset button.
The serial RS-232 interface can be used for programming and setting of system parameters.  LISTEC

®

  GmbH 

offers the terminal software LISTterm 8 for this purpose.
For the visualisation of the system status, message- and temperature-lists, as well as a graphic display of the  
temperature and alarm data, LISTgraph II and the Data Management Unit DMU 600 is available.
A LIST®controller can be used to connect and control several SCU 800 from a central point via a RS-485  
interface.

1/2

60V041-06/ 02.12.13