M7 Meter with LectroCount LCR-II Electronic Register, Optical 

Air Eliminator, High Capacity Strainer, and E-7 Valve

Optical Air Eliminator 

Refined Fuels

Mechanical Air 

Eliminator and High 

Capacity Strainer

Optical Vapor Eliminator 

LPG and NH

3

Solenoid Block 

Valve

ETVC Kit

E-7 Valve

Meter system Components

MeTer sysTeM

A Liquid Controls meter system not only accurately 

measures product, it also regulates and purifies product 

flow in order to produce the optimal conditions for 

measurement. Optimal systems typically include an air/

vapor eliminator, strainer, meter, register, and control 

valve. The LectroCount LCR-II, a register, serves as the 

central controller of the meter system. Most components 

in the meter system are hard wired to the LCR-II via data 

communication cables. See manual M100-10.

aIr/vaPor elIMInaTors

Air and vapor eliminators sense and remove air or 

vapor in the piping before it enters the metering system, 

ensuring that only liquid will pass through the meter for 

measurement. Mechanical air eliminators do not require 

a data connection to the LectroCount LCR-II (in LPG 

applications, they are often plumbed to a 3-way solenoid 

which is wired to the LectroCount LCR-II). Optical air 

eliminators use an optical sensor to monitor liquid levels 

and a solenoid-actuated valve to turn the vapor vent on 

and off. The optical sensor and the solenoid valve are 

connected to the LectroCount LCR-II by separate data 

cables. See manuals M300-20 and M300-21.

valves

Valves control the flow through a metering system. They 

open the line to initiate custody transfers and close the 

line to stop custody transfers. Some valves can partially 

close, slowing the flow rate to a dwell flow on preset 

deliveries. By slowing the flow rate, valves can lessen 

the hydraulic shock incurred by the meter system upon 

shut off and provide accurate preset deliveries. Many 

valves use solenoid-operated valves that require a hard 

wired data connection to the LectroCount LCR-II. See 

manuals M400-11 and M400-40.

eleCTronIC TeMPeraTUre volUMe 

CoMPensaTIon (eTvC) KIT

In order to perform temperature compensation 

equations, the LectroCount LCR-II relies on a 

temperature probe inserted into the strainer housing. 

Installation directions for the ETVC kit are included in 

this manual. 

MeTer sysTeM overvIeW 

Содержание LectroCount LCR-II E3655 Series

Страница 1: ...LectroCount LCR II Installation Liquid Controls Group An IDEX Fluid Metering Business Operation EM150 20 E3655 E3656 Series...

Страница 2: ...ct your local distributor Publication Updates and Translations Introduction Safety Procedures 3 ESD Protection 4 Specifications 5 Dimensions 6 LectroCount LCR II Overview 7 Meter System Overview 8 Ins...

Страница 3: ...be in accordance with the area classification for which it is used Class I Div 2 For North America installations must be per the U S National Electrical Code NFPA 70 or the Canadian Electrical Code i...

Страница 4: ...LectroCount register there are certain guidelines that must be followed to safeguard against ESD damage Registers Not Mounted Directly to the Meter In typical LectroCount installations where the Lectr...

Страница 5: ...oid 2 Output Voltage 10 2 to 27 2 VDC Current maximum 1 A maximum Solenoid 3 Output Voltage 10 2 to 27 2 VDC Current maximum 1 A maximum Optical Sensor Voltage 10 to 28 VDC Current maximum 0 5 A maxim...

Страница 6: ...6 Dimensions Side Front Top 15 9 94 5 19 LectroCount LCR II 13 7 5 8 04 10 5 70 Rear...

Страница 7: ...remote displays printers and third party devices Communications The LCR II is capable of interfacing in RS 232 and RS 485 communication protocols Housing The LectroCount LCR II housing and base are al...

Страница 8: ...data connection to the LectroCount LCR II in LPG applications they are often plumbed to a 3 way solenoid which is wired to the LectroCount LCR II Optical air eliminators use an optical sensor to moni...

Страница 9: ...ta communication with the LectroCount LCR II See manual EM300 40 Data Management Systems The DMS i1000 is an in cab computer with a heavy duty lap pad interface The DMS i1000 streamlines the flow of d...

Страница 10: ...eter Page 14 3 Run the LCR II s data and power cable to truck cab or power supply Page 17 4 Connect all components to the LCR II s CPU board 5 Mount printer and connect printer data cable Page 27 6 Co...

Страница 11: ......

Страница 12: ...ion Make sure that there are no intervening pivot points guides adjustment mechanisms etc which could interfere with the ground path between the seat cushion and the ground strap 4a If the seat cushio...

Страница 13: ...e resistance is less than 3 the system is grounded adequately 2b If the resistance is still greater than 3 check for proper metal to metal contact on both ends of the ground strap Clean any paint dirt...

Страница 14: ...essure must be relieved to zero pressure before disassembly or inspection of the strainer vapor eliminator any valves in the system the packing gland and the front or rear covers WARNING Relieving Int...

Страница 15: ...Equipment 1 Depressurize the meter completely See Warning on pg 14 2 Remove the four bolts on the bottom that fasten the register to the meter 3 Remove the adjuster from the meter 4 If the meter has a...

Страница 16: ...he kit 3 Lower the LCR II on to the bracket and securely fasten using the four bolts x provided Mount the LectroCount LCR II onto previously temperature compensated Neptune meters 1 Place the shaft ad...

Страница 17: ...he cable glands are removed from the register apply pipe sealant or PTFE tape on the gland threads before re installing Keep cables away from moving suspension components and other moving truck compon...

Страница 18: ...th the copper grease provided Insert and re coat the probe 2 or 3 times to provide a uniform coating inside the thermowell and to ensure proper heat transfer from the liquid to the probe 9 Connect the...

Страница 19: ...valves have one solenoid valve S1 and two positions an open position and a closed position Two stage valves have two solenoid valves S1 S2 and three positions open closed and dwell flow Dwell flow is...

Страница 20: ...ed to supply the dwell flow This valve is typically used in refined fuels applications A2859 11 Valve and 3 Way Solenoid A two stage valve with a S2 solenoid operated valve and a 3 way solenoid valve...

Страница 21: ...re valves to the LCR II 1 Attach cable glands and or conduit connectors to the solenoid valve s and the LCR II port s 2 Thread the wires through piece of weatherproof conduit that is cut to length fro...

Страница 22: ...T relay switch 1 per solenoid 20 AWG stranded wire 2 per solenoid Weatherproof flexible conduit diameter and NPT conduit connectors or cable glands PTFE tape or pipe sealant 84040 Board To wire 110 VA...

Страница 23: ...air or vapor eliminator 20 AWG stranded wire 2 for the S3 solenoid valve Weatherproof flexible conduit diameter and NPT conduit connectors or cable glands PTFE tape or pipe sealant To wire optical air...

Страница 24: ...R II port 3 Run the weatherproof conduit between the POD and the LCR II housing pull the wires through the ports and tighten the connectors 4 Connect the four POD terminals to four terminals on the J1...

Страница 25: ...g terminal J16 into the 81944 board 7 Route the P transducer cable through a cable gland in a port on the back of the LCR II Secure the cable gland LC recommends running the cable through weatherproof...

Страница 26: ...types of displays Signals from these outputs duplicate the volume data sent to the LCR II display Refer to the LectroCount remote display manual for complete installation instructions To wire an exter...

Страница 27: ...e from the back of the truck to the cab To communicate via true RS 232 protocol the VP Red wire must be connected to the J3 terminal block at terminal 47 not 46 RS 232 Communication Epson Printer Grou...

Страница 28: ...he table below 52 53 54 55 56 PRINTER SERIAL 485 TERMINAL POWER COUNTER MH1 CTS RXD TXD RTS GND GND 485 A 485 B CTS RXD TXD RTS VP EARTH AUX OUTPUTS PULSE INPUTS AUX I O GND GND GND IN 1 OUT1 OUT2 OUT...

Страница 29: ...harge the battery in accordance with the manufacturer s specifications Ensure the alternator is large enough to meet the total demands of the truck including the LCR II The LCR II requires a minimum o...

Страница 30: ...the 7 5A fuse into the red wire Make the splice close to the direct power terminal connection in the accessory panel and on the power side of the splice made with the printer power cable Power Check...

Страница 31: ...Line Fuse Drain Wire GROUND Accessory Panel Direct Power Supply POWER J6 DC 11 12 13 Gray Power Cable see below Black Data Cable 7 5A In Line Fuse Black Red Red Accessory Panel Chassis or Reliable Gr...

Страница 32: ...the groove and tighten the cover screw securely 3 Shaft Seals Units with internal pulsers have an O ring around the pulse encoder drive shaft that extends through the bottom of the LCR housing If a dr...

Страница 33: ...LCR II W O Pulser and Net Gallons Tag 818272 E365637 LCR II W Pulser and Gross Litres Tag 818273 E365537 LCR II W O Pulser and Gross Litres Tag 818273 E365647 LCR II W Pulser and Net Litres Tag 818274...

Страница 34: ...B 11 10 12 13 52 53 54 55 56 24 25 81833 Hollow O ring Seal 81330 Coiled Cable Handset 81513040 Data Cable 81841 81840 Enclosure Base Assy w Pulser w o Pulser 71319 Desiccant 84040 CPU Board Assy 081...

Страница 35: ...Connector 81320 J6 3 Pin Connector 81392 J8 8 Pin Connector 81391 J12 7 Pin Connector 81321 J13 6 Pin Connector 81837 J15 5 Pin Connector 81322 J14 4 Pin Connector 11 12 13 81324 J1 5 Pin Connector 8...

Страница 36: ...0 60 60 Liquid Controls 105 Albrecht Drive Lake Bluff IL 60044 847 295 1050 SAMPI Via Amerigo Vespucci 1 55011 Altopascio Lucca Italy 39 0583 24751 IDEX Fluid and Metering Pvt Ltd Survey No 256 Alindr...

Отзывы: