LCR.iQ - Setup and Operations Manual
48
Get the latest PDF manual:
https://www.lcmeter.com/resources/technical/manuals
Mobile/online version of this manual:
https://www.lcmeter.com/manuals
Auxiliary 1 Output
A list box that determines how any digital output that is set to AUX 1 will operate on the
selected product. To control external components, there are several features in the LCR.iQ
that can be set to perform according to the Auxiliary 1 and Auxiliary 2 settings. This includes
pumps, injectors, PTO, throttle, alarms, and reset pulse, among others.
Options:
·
Off
– Any output set to AUX 1 Calibration Mode Settings will always be off (inactive).
·
On
– Any output set to AUX 1 Calibration Mode Settings will always be on (Active and
Sinking to ground).
·
On - During Active Delivery
– Any output set to AUX 1 Calibration Mode Settings will
turn
on (Sink to ground) when a delivery is started. It will turn off when the delivery is
complete.
·
On - During Run State
– Any output set to AUX 1 Calibration Mode Settings will turn on
(Sink to ground) when a delivery is active and not paused. The output will be on when a
delivery begins. However, if the delivery pauses, the output will turn off until the delivery
resumes. If the
End of delivery
command is given, the output will remain off and the
delivery will end.
·
On - Flow Rate Monitor
– Any output set to AUX 1 Calibration Mode Settings will be on
when a delivery is active. However, it will deactivate if the flow rate meets or exceeds 40
units/time. If the flow rate does not meet or exceed 40 units/time, the output will remain
on.
·
On - Reverse Flow
– Any output set to AUX 1 Calibration Mode Settings will be off when
a delivery begins. It will only turn on when the register detects flow in the negative or
reverse direction.
·
Reset Pulse/Delivery Start
– For any delivery that uses 3rd-party remote counters
requiring a reset pulse to 0.0, any output set to AUX 1 Calibration Mode Settings will
output a short pulse at the start of a delivery.
·
Toggle Flow Rate
– Any output set to AUX 1 Calibration Mode Settings will turn on once
the flow rate of the LCR.iQ exceeds the set flow rate point in the
Auxiliary 1 Flow Rate
Toggle
field. See below.