background image

Warning:

 Use only water or an 

appropriate antifreeze. Do not use any 
other liquids especially methanol, 
automotive antifreeze or any kind of oil.
Do not exceed 50% antifreeze.

LION

BOILERS

CEBR2 Series Boiler

Installation Manual

TM

CEBR2 V7.0

Printed in Canada

Содержание CEBR2 Series

Страница 1: ...n appropriate antifreeze Do not use any other liquids especially methanol automotive antifreeze or any kind of oil Do not exceed 50 antifreeze LION BOILERS CEBR2 Series Boiler Installation Manual TM C...

Страница 2: ...2...

Страница 3: ...volt single phase power to terminals L1 and L2 and connection of a neutral conductor to the N terminal see Fig 4 Three phase models require connection of three phase power of the correct voltage to th...

Страница 4: ...erature increases outdoors the heat output of the boiler will be decreased For example when it is 10 C outside the water temperature will be 32 C and when it is 5 C outside the water temperature will...

Страница 5: ...40 32 CEBR2 208 11 11 25 208 3 31 2 40 32 CEBR2 208 15 14 7 208 3 40 8 60 48 CEBR2 208 22 22 5 208 3 62 5 100 80 CEBR2 208 30 29 4 208 3 81 6 125 100 CEBR2 600 15 14 7 600 3 14 1 20 16 CEBR2 600 30 2...

Страница 6: ...g system Pressure will decrease at a rate of 0 433 psi per foot above the fill point An expansion tank must be included to allow for approximately 4 expansion of the water in the entire heating system...

Страница 7: ...d as Zero Clearance may be mounted against combustible surfaces 4 Units must be mounted straight as shown in Fig 2 with the outlet at the top and the inlet on the bottom See Up Arrow on label on side...

Страница 8: ...control board are closed and stop when these terminals are opened Thermostat 1 terminals STAT 1 controls pump 1 and thermostat 2 terminals STAT 2 control pump 2 the priority terminals Thermostat Conne...

Страница 9: ...e being used Temperature Control Setting Aquastat The boiler has a temperature control knob known as an aquastat on the left hand side This sets the maximum temperature that the boiler will operate at...

Страница 10: ...d thoroughly purged of air The automatic air vent is to assist in removing air from the top of the tank to prevent elements from burning out It alone is not sufficient in removing air from the entire...

Страница 11: ...cipator setting Check pump circulation Boiler operates continuously Check anticipator setting Boiler noisy Oversized pump Flow rate too high Flow rate too low Pump location incorrect Boiler not heatin...

Страница 12: ...inal purchase price to the current owner of the Boiler regardless of any prior attempt by the Manufacturer to repair or replace that Boiler The obligation of the Manufacturer to repair replace or refu...

Страница 13: ...HETHER EXPRESS OR IMPLIED AND ALL SUCH OTHER WARRANTIES INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED AND EXCLUDED FROM T...

Страница 14: ...14...

Страница 15: ...15...

Страница 16: ...16...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...voltage at any of the elements then the element relay for that element is stuck on and needs to be replaced 2 Check the fuse on models equipped with a fuse a Remove the fuse located inside the boiler...

Страница 21: ...trol board the one with the two gray wires b If the indicator lights now come on after waiting for the one to two minute delay between each element the temperature sensor needs to be replaced If the i...

Страница 22: ...ach element with an ohm meter and replace any elements as necessary If you have gone through the above steps and the boiler is still not working please contact us for assistance Concept Manufacturing...

Отзывы: