Instruction Manual 

   

MC-700 Series

 

  

Safety Precautions 

 

 
Incorrect handling may cause death or injury

 

 

(1)

 

Before connecting the fittings, check that no damage or  defects are found on 
the  fittings.  Make  connections  properly  and  make  sure  that  a  leak  test  is 
conducted  before  actual  operation  to  prevent  fluid  from  leaking  into  the 

atmosphere (Hereafter, the measured fluid is called “gas” or “fluid”).

 

(2)

 

DO NOT apply any fluids corrosive to materials exposed to gas. Corrosion may 
cause fluid to leak into the atmosphere. Check the gas type to be used in advance.

 

(3)

 

This device is not designed as an explosion proof structure. DO NOT use this 
device in a place where explosion-proof structures are required. Doing so may 
cause fire or explosion.

 

 

Incorrect handling may lead to medium or slight injury or may 
cause damage to, or loss of, facilities or equipment

 

 

(1)

 

Observe the precautions listed in the WARNING (above)

 

(2)

 

Strictly  observe  the  electrical  specifications.  Not  doing  so  may  cause  fire, 
damage to sensors or malfunction.

 

(3)

 

This  device  is  not  designed  to  be  waterproof.  DO  NOT  locate  this  device 
outdoors or in a place where it may be splashed with water. Doing so may cause 
fire, trouble, or malfunction of the device.

 

(4)

 

DO NOT modify this device. It may cause fire or other problems. 

(5)

 

This  device  is  not  designed  to  handle  hot  swap.  Please  avoid  attaching  and 
removing the power supply connector and interface connector with the power 
switched on. Attachment and/or removal with the power on may result in failure 
of the device. 

(6)  While  a  power  supply  is  applied  to  MFC,  ±15VDC  must  be  applied 

simultaneously. If only +15VDC or -15VDC is applied, electronic circuits will 
become unstable and it may cause a malfunction of MFC.

 

(7)

 

This device is a precious device, please handle it carefully. Dropping down or 
handling  it  carelessly  will  cause  damage.  Please  use  assist  instrument  while 
moving or setting the device.

 

(8)

 

Regular  maintenance  is  recommended  for  steady  use  of  this  device 
(Recommended proofreading frequency is once a year). 

 

 

1. Introduction 

   

This manual explains basic operation of the MC-700 series (Hereafter, it is called 
"MFC").  Please  read  through  this  manual  and  other  separate  volumes  (Digital 
Interface  Manual,  Special  Function  Manual,  Command  Chart)  carefully  to 
familiarize yourself with the features of this device. 

 

2. Summary 

   

This device is the mass flow controller with the function of switching different 
kinds of gas and flow rate (Hereafter called "variable function" or "VR"). By using 
the 3 rotary switches on the MFC, the gas type and flow

 

rate can be changed. The 

rotary switches are placed conveniently on top of the MFC unit so

 

that 

adjustments can be made accordingly even after the unit is set in position. For old 
models, stocking MFC for each of gas and flowrate was necessary because only 
one spec is available to one MFC, and MC-700 can reduce your stocking because 
it can be used for more than one spec with one MFC. 

 

3. Features 

The MFC has the following features. 
(1) LINTEC’s proprietary ambient temperature compensation type flow sensor. 
     

·

The influence of ambient temperature is small due to the sensor temperature 

     

 

control following the ambient temperature.   

   

·

Since the temperature distribution of the sensor is constant, high-speed response 

   

 

is possible. 

(2) Gas type and flow rate  setting can be changed by using the 3 switches on the 

mass flow controller unit. 

(3) Digital interface (RS-485) is standard equipment and the maximum of 32 MFCs 

could be connected together with daisy chain. 

     

(Option: Digital interface RS-232C is possible)   

(4) Small structure of dead volume using diaphragm valve. 
(5) Stainless steel 316L is used because of good corrosion resistance and seal ability. 
(6) Particule-free structure 
(7) RoHS compliant, 

CE conformity

 

 
4. Structure 

   

The  MFC  consists  of  sensors,  bypass,  valves,  and  a  microcomputer  for  signal 
processing. A digital PID feedback control system controls the valve action so that 
flow rate output from the sensor agrees with flow rate setting value. 

 
 
 
 
 
 
 
 
 
 
 

5. Specification / Dimensions 

(1) Specification 

Name 

Mass Flow Controller 

Model 

MC-710 

MC-720 

MC-730 

Standard flow rate in 
nitrogen VR number 

10SCCM to 3SLM 
(VR number 02 to 06) 

3.1 to 10SLM 

(VR number 07) 

11 to 50SLM 

(VR number 08 and 09) 

Valve operation mode 

Normally closed / Normally open 

Internal surface treatment 

No treatment / Precision polishing 

Flow rate control range 

2% of full scale 

Analog flow rate setting 
signal 

Proportional to flow rate: 0 to 5VDC 

Analog flow rate output 
signal 

Proportional to flow rate: 0 to 5VDC 

Variable function (VR) 

Changeable by using rotary switches (0.50 to 2.00) 
Range is limited by original flow rate range of unit 

Accuracy (Note1) 

±1.0%F.S. 

Repeatability (Note1) 

±0.2%F.S. 

Response time 

1sec (Typical) 

Operating differential 
pressure (Note2) 

50 to 300kPa 

100 to 300kPa 

150 to 300kPa 

Maximum operating 
pressure 

300kPa(G) 

Withstanding pressure 

1MPa(G) 

Operational temp/ 
Humidity range 

5 to 50°C / 0 to 80%RH (with no condensation) 

(Accuracy insurance 15 to 35°C) 

Storage temp /   
Humidity range 

0 to 60°C / 0 to 80%RH (with no condensation) 

Leak integrity 

Less than

 

1×10

-11

Pa·m

3

/sec (He) 

Mounting direction 

Free 

Materials exposed to gas 

Stainless steel 316L, PCTFE, PTFE 

Seal materials 

Stainless steel 316L 

Actuator 

Piezo electric actuator 

Fitting 

6.35VCR

 

Type: 124mm 

6.35VCR 

 

Type: 106mm (option) 

6.35SWL 

 

Type: 127mm (option) 

Power supply 

+15VDC±3%: 120mA      -15VDC±3%: 50mA 

Analog interface 

D-sub 9pin (male), Fixed size of screw:M3 

Digital interface 

RS-485 (RJ45 Jack) 2-wire

 

Maximum connection 32 units 

RS-232C (RJ45 Jack) Maximum connection 100units (R0/R1 Option) 

Weight 

Approx. 1 kg 

Note 1) The value at the time of shipping. This may change with usage of VR function. 
Note 2) The value at the time of shipping. This may change with gas type and flow rate setting. 

 

   

·

 

Connect the MFC to the ground. 

(2) Dimensions 

 

 

 

 

 

 

 

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

6. Ordering information 

MC-710 MC - 4VR2 A0A0A0

 

- 06 - N2 - 1.5SLM 

 

[1]

   

 

  [2]

 

                         

[3]

     

 

[4]

   

       

               

[5]

 

     

[6]

     

         

  [7]

 

 

               

[1] Model: MC: Mass Flow Controller Series    MC-710

 

MC-720

 

MC-730 

[2] Valve operation mode · Internal surface treatment 

NO: Normally opened valve / No treatment 
NC: Normally closed valve / No treatment 
MO: Normally opened valve / Precision polishing 
MC: Normally closed valve / Precision polishing 

[3] Fitting 

     

4VR2: 6.35VCRType 124mm 

     

4VR1: 6.35VCRType 106mm (option) 

     

4SWL: 6.35SWLType 127mm (option)

   

 

 

Please consult us for other fitting types. 

[4] Other options 

           

Default settings is labeled “A0A0A0”, please consult for more information. 

[5] VR Number 
[6] Gas type 
[7] Full scale flow rate and unit:    SCCM(0°C standard),

 

SLM(0°C standard) 