4 Electrical connection
4.1 Motor Cable
Do not connect or disconnect motor when there is power on the servo drive.
Use only double-shielded original LinMot cable. Cables from other sources must be
checked precisely before commissioning.
Incorrect connections can destroy the drive and stator.
The stator is connected to protective earth via the motor cable. The screw connections of
R connector must be tightened up to the stop.
Three types of cables are available for linear motors. The standard motor cable is intended
for stationary installation. The High-Flex cable (suitable for trailing chains) and the robot
cable are used for moving cable applications. The connector cable integrated in the stator is
20 cm or 150 cm (R20 or R150) long depending on the stator variant and must not be
moved.
4.1.1 Technical Data of the Stator Cable
PS01-23x80F-HP-SSCP-R20
PS01-23x160H-HP-SSCP-R20
PS01-23x80F-HP-SSCP-R150
PS01-23x160H-HP-SSCP-R150
Cable name
KS03-04/05
KS03-04/05
Cable length
200 mm
1500 mm
Minimum bending radius for
fixed installation
25 mm
(0.98 in)
25 mm
(0.98 in)
Minimum bending radius
when moving
Not suitable for applications with
moving motor cable.
Not suitable for applications with
moving motor cable.
Approval
UL / CSA 300V
UL / CSA 300V
Material wire insulation
TPE-U
TPE-E
Material cable sheath
PUR
PUR
Permissible temperature
-
40 °C…+80 °C
Oil resistance
very good acc. DIN VDE 0282
Part 10 + HD 22.10
very good acc. DIN VDE 0282
Part 10 + HD 22.10
Chemical resistance (to
acids, alkalis, solvents,
hydraulic fluid)
good
good