Installation Guide Servo Drives
ENG
NTI AG / LinMot
C1250-MI
Page 15 / 29
10
System LED Blink Codes
LED Blink Codes
Error
Warn
EN
Description
Off
Warning
Operation
Enabled
Normal Operation:
Warnings and operation enabled are displayed.
On
● ~2 Hz
0..15 x
Error Code
High Nibble
● ~2 Hz
0..15 x
Error Code
Low Nibble
Error:
The error code is shown by a blink code with “WARN” and “EN”
The error byte is divided into low and high nibble (= 4 bit).
”WARN” and “EN” are
blinking together.
The error can be acknowledged.
(e.g.: WARN blinks 3x, EN blinks 2x; Error Code = 32h)
● ~2 Hz
● ~2 Hz
0..15 x
Error Code
High Nibble
● ~2 Hz
0..15 x
Error Code
Low Nibble
Fatal Error:
The error code is shown by a blink code with
“WARN” and “EN”.
The error byte is divided into low and high nibble.
”WARN” and “EN” are blinking together.
Fatal errors can only be acknowledged by a reset or power cycle.
(e.g.: WARN blinks 3x, EN blinks 2x; Error Code = 32h)
● ~4 Hz
● ~2 Hz
0..15 x
Error Code
High Nibble
● ~2 Hz
0..15 x
Error Code
Low Nibble
System Error:
Please reinstall firmware or contact support.
● ~0.5 Hz
● ~0.5 Hz
On
Signal Supply 24V too low:
The error and warn LEDs blink alternating if the signal 24 VDC (X4.2) is less than 18
VDC.
Off
○●●●
●○●●
Plug&Play Communication Active:
This sequence (Warn on, then En on, then both off, complete sequence of the 4 states ca. 1
s) signalizes the state when the plug and play parameters are being read from the motor.
○●
~4 Hz
●○
~4 Hz
Off
Waiting for Defaulting Parameters:
When ID (S1, S2) is set to 0xFF, the drive starts up in a special mode and the Error and Warn
LED blink alternating ~4 Hz. When the ID ist set to 0x00, all parameters will be set to their
default value. To leave this state, power down the drive and change the ID. Also see in the
Usermanual_LinMot-Talk under chapter trouble shooting.
Off
○ ●
~2 Hz
○●
~2 Hz
Defaulting Parameters Done:
When the parameters have set to their default values (initiated via S1/S2 on power up) the
Warn and En LEDs blink together at 2 Hz. To leave this state, power down the drive. Also see
in the Usermanual_LinMot-Talk under chapter trouble shooting.
On
On
On
Bootstrap
If also both RT LEDs are on, the drive is in the bootstrap mode. Set S5 to off.
The meaning of the error codes can be found in the
Usermanual_MotionCtrl_Software_SG5-SG7
and the user manual
of the installed interface software. These documents are provided together with LinMot-Talk configuration software
and can be downloaded from www.linmot.com.
Содержание 0150-5590
Страница 7: ...Installation Guide Servo Drives ENG NTI AG LinMot C1250 MI Page 7 29 4 Interfaces ...
Страница 23: ...Installation Guide Servo Drives ENG NTI AG LinMot C1250 MI Page 23 29 17 1 IECEE CB SCHEME CB test certificate ...
Страница 24: ...Installation Guide Servo Drives ENG Page 24 29 C1250 MI NTI AG LinMot ...
Страница 26: ...Installation Guide Servo Drives ENG Page 26 29 C1250 MI NTI AG LinMot 17 2 UL Listing ...