iGrow 800 Quick Setup Guide 

SETTING UP SETPOINTS 
With the iGrow 800 you can program Temperature, Relative Humidity, and C02 Setpoints. 
Please view the following video and necessary steps in setting up your setpoints  

 

IGrow 800 – Setpoint Programming 

http://www.youtube.com/watch?v=7JGrg_Q1taQ 

 

 

 

Cool Setpoint - if the temperature goes above this threshold it will enter into the cooling stages to bring the temperature 
back in line within the Normal temperature range (you can have up to 6 cool stages) 
Heat Setpoint - if the temperature goes below this threshold it will enter into the Heating stages to bring the temperature 
back in line within the Normal temperature range (you can have up to 2 heat stages) 
Humidify Setpoint - if the RH reading is below this parameter, the condition is considered too dry, and the system will go 
into the humidification stage. 
Dehumidify Setpoint - if the RH reading is above this parameter, the condition is considered too damp, and the system will 
go into the dehumidification stage. 
C02 Setpoint - if the C02ppm level is blow this parameter, the condition will be Low C02, and the system will start injecting 
C02 until it reaches the Setpoint plus Deadband. 

  

There are three options in temperature, 
humidity and C02 setpoints 

•   DAY 
•   NIGHT 
•   DIF 
 
DAY is active by default. NIGHT and DIF can be 
turned on if desired. 
To turn on a setpoint that is disabled simply 
highlight Set – Night or Set – DIF hit OK 
It will display that the setpoint is currently 
off.  To enable it on press button #5 (turn 
setpoint on/off) which will then display the 
night setpoint screen 
 
 
Deadbands 
while cooling or heating equipment may be engaged as soon as the measured temperature falls outside of the normal 
range, a deadband will prevent the equipment from shutting off when the temperature returns to slightly within the normal 
range.  Deadbands keeps equipment from cycling on and off repeatedly due to small temperature fluctuations.  The same 
concept applies with humidification and dehumidification. 

 

Содержание iGrow 800

Страница 1: ... above this parameter the condition is considered too damp and the system will go into the dehumidification stage C02 Setpoint if the C02ppm level is blow this parameter the condition will be Low C02 and the system will start injecting C02 until it reaches the Setpoint plus Deadband There are three options in temperature humidity and C02 setpoints DAY NIGHT DIF DAY is active by default NIGHT and D...

Страница 2: ...the Normal temperature range the iGrow 800 will enter cooling or heating stages to bring it back in line With the iGrow 800 you can program up to six cooling and two heating stages These stages go from Cool 1 to Cool 6 and Heat 1 to Heat 2 Cool 1 and Heat 1 are the least aggressive with Cool 6 and Heat 2 the most aggressive In your program you will determine what equipment you want to be active in...

Страница 3: ...Dehumidify High Humidity setpoint Cold De humidify is engaged when out temp goes below the threshold value set in advanced screen The arrows buttons 5 thru 8 are used for moving the highlight to the desired stage The Setup and OK buttons are used to select or deselect the highlighted stage for a device For dual channel devices vents curtains the second channel is disabled as shown For Curtains 0 c...

Страница 4: ...low out temp option Wheel can be used to change the values The LowOutTemp threshold is the outside temperature below which the dehumidification stage will revert to its Cold dehumidification state For example you may want to dehumidify but if it s very cold outside you may want to turn on the heat instead of open a vent and turning on a fan Cycling Program if no Humidity Sensor is present This hum...

Страница 5: ...RS vA iGrow 800 Programming Expansion Outputs https www youtube com watch v OjRvULzwwvk LinkConn 100 Software Overview https www youtube com watch v 2VUD426h6Co iGrow 400 800 Connecting with The iGrow Cloud https youtu be DobvKzIW56E iGrow 400 800 Connecting LinkConn 100 Software https youtu be CR0bpSkwd0 iGrow 400 800 Networking Multiple Controllers https youtu be 07tg4k fa_8 iGrow 400 800 Restor...

Страница 6: ...ww youtube com watch v C49pp1g LxM iGrow800 Saving History and USB Logging https www youtube com watch v DQ3xvABTk94 If you have any more questions or if you need assistance please give us a call at 714 975 9474 or email us at support link4Corp com ...

Отзывы: