Power supply
AC/DC
24 (18-32) V
Cable
Max outer diameter
7 mm
Power consumption
0,4 W
Power consumption
For wiring
0,5 VA
Degree of protection
EN 60529
IP44
Tightness class to the environment
EN 12237
D
Storage temperature range
-30 to +50 °C
Maximum ambient moisture
95 % RH
Connection
RS485 standard or analog
Cable
RS485 standard cable, 2-wire shielded twisted
pair, min. 0,1 mm² (LIYCY cable)
Protocol
Modbus
Output
Flow
Flow
Velocity
Temperature
m³/h
l/s
m/s
°C
Velocity range
For guaranteed measurement uncertainty
0,2 - 15,0 m/s
Measurement uncertainty flow
(assuming correct installation)
Depending on which is the greatest of the per-
centage or the absolute number for the specific
products size.
±5
Dim. 100 = ±1,00
Dim. 125 = ±1,25
Dim. 160 = ±1,60
Dim. 200 = ±2,00
Dim. 250 = ±2,50
Dim. 315 = ±3,15
Dim. 400 = ±4,00
Dim. 500 = ±5,00
Dim. 630 = ±6,00
% or
l/s
l/s
l/s
l/s
l/s
l/s
l/s
l/s
l/s
Temperature range
-10 to +50 °C
Measurement uncertainty temperature
±1 °C
Bluetooth radio
Frequency
2402 — 2480 MHz
Output
-40 to +9 dB
Airflows
Ø [mm]
0,2 m/s
7,0 m/s
15,0 m/s
m³/h
l/s
m³/h
l/s
m³/h
l/s
100
6
2
198
55
425
118
125
9
3
309
86
662
184
160
14
4
507
141
1087
302
200
23
6
792
220
1696
471
250
35
10
1237
344
2650
736
315
56
16
1964
546
4208
1169
400
90
25
3167
880
6786
1885
500
141
39
4948
1374
10603
2945
630
224
62
7855
2182
16833
4676
Technical data