A-6
INSTALLATION
SP-125 PLUS
CODE REQUIREMENTS FOR INPUT
CONNECTIONS
This welding machine must be connected to
power source in accordance with applicable elec-
trical codes.
The United States National Electrical Code (Article
630-B, 1990 Edition) provides standards for amperage
handling capability of supply conductors based on
duty cycle of the welding source.
If there is any question about the installation meeting
applicable electrical code requirements, consult a
qualified electrician.
Requirements For Rated Output
A power cord with a 15 amp, 125 volt, three prong
plug (NEMA Type 5-15P) is factory installed on the
SP-125 Plus. Connect this plug to a mating grounded
receptacle which is connected to a 20 amp branch cir-
cuit with a nominal voltage rating of 115 to 125 volts,
60 Hertz, AC only.
The rated output with this installation is 90 amps, 18
Volts, 20% duty cycle (2 minutes of every 10 minutes
used for welding).
Do not connect the SP-125 Plus to an input power
supply with a rated voltage that is greater than 125
volts.
Do not remove the power cord ground prong.
Requirements For Maximum Output
In order to utilize the maximum output capability of the
machine, a branch circuit capable of 25 amps at 115
to 125 volts, 60 Hertz is required. This generally
applies when welding steel that is equal to or greater
than 12 gauge, 0.105” (2.5 mm) in thickness.
Requirements For CSA Rated Output
A line cord with a 15 amp, 125 volt, three-prong plug
(NEMA Type 5-15P) is factory installed. Connect this
plug to a mating grounded receptacle which is con-
nected to a 15 amp branch circuit with a nominal volt-
age rating of 115 volts to 125 volts, 60 hertz, AC only.
With this installation, the SP-125 Plus can be used at
an output of 63 amps, 20 volts, 20% duty cycle.