A Humidity and Temperature Controller 

Version A1.01a 

Specification 

Power supply:    

 

12Vac, or 12Vdc 

Input:   

 

 

 

One humidity and temperature sensor, wire length 1.5 meters, system will be   
stable when the wire length is up to 50 meters 

Sensor precision:     

Humidity ±3% RH@25

; Temperature ±1%@25

 

Setting range:    

 

Humidity 0.0 

  99.9% RH; Temperature 0.0 

  80.0

℃ 

Output:     

 

 

Every output ≤ 7A (250Vac, pure resistance)   

Working environment:    -10 

  45

; ≤ 90% RH without dew 

Power consumption: 

2W 

Display 

When the sensor is not connected well, or fails, display shows “--.-“. 
When the temperature output is energized, the up LED “out” is on; 
When the humidity output is energized, the bottom LED “out” is on. 

 
Setting Operation 

Keep

S

depressed for 2 seconds to enter into set status: 

The up window displays the parameter code. 
The bottom window displays the value of the code. 

Press

S

to select the code: S01->S02->SC1->S03->S04->SC2. 

Press

or

  to set the value (keep depressed make fast set). 

Keep

S

depressed for 2 seconds to exit, and the settings are saved. 

Note: The status will exit if no key operation for 30 seconds, and the settings will be saved. 

Code 

Function 

Set Range 

Remark 

Factory Set 

SO1 

Temperature output energized 

0.0 ~ 99.9℃ 

Set point for on 

22.0 

SO2  Temperature output de-energized 

0.0 ~ 99.9℃ 

Set point for off 

20.0 

SC1 

Temperature calibration 

-5.0 ~ 5.0℃ 

 

 0.0 

SO3 

Humidity output energized 

0.0 ~ 99.9% RH 

Set point for on 

10.0 

SO4 

Humidity output de-energized 

0.0 ~ 99.9% RH  Set point for off 

20.0 

SC2 

Humidity calibration 

-5.0 ~ 5.0% RH 

 

 0.0 

 

Control Function 

Temperature control 

If SO1 = SO2, there will be no temperature control function. 
If SO1 < SO2, work in heating mode: 

When Troom ≤ SO1, temperature output energized; 
When Troom ≥ SO2, temperature output de-energized. 

If SO1 > SO2, work in cooling mode: 

When Troom ≥ SO1, temperature output energized; 
When Troom ≤ SO2, temperature output de-energized. 

 